Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Apr 13, 2020, 08:42 AM
  • 01 1184_01 1183_04132020_020031.mp4

Date
04/13/2020
W/O
823723
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00225
PipeID
P02038
Time
1:42 AM
Certificate
U-508-7069
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K7562
Sewer Name
01 WILCOX AVENUE TRUNK
City
BELL
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 01
Page No.
05
Purpose
Routine Assessment
Project
RFIR_WO_823723_TV01072_APR2020
Sewer Type
Gravity
Material
NRCP
Shape
Circular
Height
15 in.
Width
15 in.
Upstream MH
01 1184
Downstream MH
01 1183
Dir. of Survey
Downstream
Length Surveyed
304.2 ft.
Total Length
304.2 ft.
Structural Index
3
Structural Quick
3K21
Structural Rating
188
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
3
Overall Quick
Overall Rating
188
Pipe schematic from manhole 01 1184 to 01 1183
MH: 01 1184MH: 01 1183downstream0 ft. MWL - Water Level, 15 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 01 11840 ft. MWM - Water Mark, 35 %of cross sectional area0 ft. MGO - General Observation - CONNECTION AT MH 3 O'CLOCK0 ft. MGO - General Observation - CONNECTION AT MH 9 O'CLOCK2 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start59.2 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"61.4 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"65.1 ft. FL - Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES73.8 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"101.5 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"111.5 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"134.2 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"137.8 ft. CL - Crack Longitudinal, at 02 o'clock, within 8 inches of joint: YES152.3 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"160 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"192.6 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"195.3 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"233 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"262.9 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"264.3 ft. TFA - Tap Factory Made Active, at 10 o'clock, -, within 8 inches of joint: NO, 6"293.5 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"296 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"298.9 ft. FL - Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES304.2 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish304.2 ft. AMH - Downstream Manhole, Survey Ends - 01 1183

Observation photos (4)

  • Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    2 ft. - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES

    65.1 ft. - Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES

  • Crack Longitudinal, at 02 o'clock, within 8 inches of joint: YES

    137.8 ft. - Crack Longitudinal, at 02 o'clock, within 8 inches of joint: YES

  • Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES

    298.9 ft. - Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES

Observations (26)

DistanceCodeObservation
293.5TF
0MWL
101.5TF
2SAP
59.2TF
262.9TFC
137.8CL
0AMH01 1184
192.6TF
304.2SAP
61.4TF
0MWM
134.2TF
264.3TFA
298.9FL
296TF
233TF
0MGOCONNECTION AT MH 3 O'CLOCK
111.5TF
160TF
65.1FL
195.3TF
304.2AMH01 1183
0MGOCONNECTION AT MH 9 O'CLOCK
73.8TF
152.3TF

Properties (6)

additional_info
SC411121
custom_field_two
3
customer
LACSD
datetime
2020-04-13T01:42:00-07:00
documentation
PROPIPE
is_lateral_inspection
false