Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Apr 13, 2020, 10:57 AM
  • 01 1176_01 1175_04132020_041704.mp4

Date
04/13/2020
W/O
823723
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00225
PipeID
P02028
Time
3:57 AM
Certificate
U-508-7069
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K7562
Sewer Name
01 WILCOX AVENUE TRUNK
City
BELL
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 01
Page No.
08
Purpose
Routine Assessment
Project
RFIR_WO_823723_TV01072_APR2020
Sewer Type
Gravity
Material
NRCP
Shape
Circular
Height
15 in.
Width
15 in.
Upstream MH
01 1176
Downstream MH
01 1175
Dir. of Survey
Downstream
Length Surveyed
376.4 ft.
Total Length
376.4 ft.
Structural Index
3
Structural Quick
3O21
Structural Rating
236
O&M Index
2
O&M Quick
2111
O&M Rating
3
Overall Index
3
Overall Quick
Overall Rating
239
Pipe schematic from manhole 01 1176 to 01 1175
MH: 01 1176MH: 01 1175downstream0 ft. AMH - Upstream Manhole, Survey Begins - 01 11760 ft. MWM - Water Mark, 30 %of cross sectional area0 ft. MWL - Water Level, 15 %of cross sectional area0 ft. MGO - General Observation - CONNECTION AT MH 3 O'CLOCK3.4 ft. MGO - General Observation - MAG COAT3.4 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start49.9 ft. FL - Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Start51.3 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"55.9 ft. FL - Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Finish69.2 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"99.9 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"107.7 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"146.7 ft. TFA - Tap Factory Made Active, at 10 o'clock, -, within 8 inches of joint: NO, 6"183.9 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"201.6 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"224.9 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"248.8 ft. CL - Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES248.8 ft. RFB - Roots Fine Barrell, at 12 o'clock, within 8 inches of joint: YES251.2 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"251.2 ft. RFL - Roots Fine Lateral, at 10 o'clock298.3 ft. FL - Fracture Longitudinal, at 10 o'clock, within 8 inches of joint: YES299.1 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"301.7 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"340.4 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"376.4 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish376.4 ft. AMH - Downstream Manhole, Survey Ends - 01 1175376.4 ft. MGO - General Observation - CONNECTION AT MH 9 O'CLOCK

Observation photos (5)

  • Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    3.4 ft. - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Start

    49.9 ft. - Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Start

  • Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES

    248.8 ft. - Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES

  • Roots Fine Barrell, at 12 o'clock, within 8 inches of joint: YES

    248.8 ft. - Roots Fine Barrell, at 12 o'clock, within 8 inches of joint: YES

  • Fracture Longitudinal, at 10 o'clock, within 8 inches of joint: YES

    298.3 ft. - Fracture Longitudinal, at 10 o'clock, within 8 inches of joint: YES

Observations (27)

DistanceCodeObservation
51.3TF
3.4MGOMAG COAT
340.4TF
201.6TF
301.7TF
251.2TF
0AMH01 1176
183.9TF
55.9FL
146.7TFA
0MWM
376.4SAV
3.4SAV
107.7TF
298.3FL
251.2RFL
0MWL
49.9FL
0MGOCONNECTION AT MH 3 O'CLOCK
224.9TF
99.9TF
299.1TF
248.8CL
376.4AMH01 1175
376.4MGOCONNECTION AT MH 9 O'CLOCK
69.2TFC
248.8RFB

Properties (6)

additional_info
SC411121
custom_field_two
3
customer
LACSD
datetime
2020-04-13T03:57:57-07:00
documentation
PROPIPE
is_lateral_inspection
false