Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Apr 14, 2020, 05:21 AM
  • 01 1173_01 1172_04132020_223745.mp4

Date
04/13/2020
W/O
823723
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00225
PipeID
P02024
Time
10:21 PM
Certificate
U-508-7069
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K7563
Sewer Name
01 WILCOX AVENUE TRUNK
City
BELL
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 01
Page No.
08
Purpose
Routine Assessment
Project
RFIR_WO_823723_TV01072_APR2020
Sewer Type
Gravity
Material
NRCP
Shape
Circular
Height
15 in.
Width
15 in.
Upstream MH
01 1173
Downstream MH
01 1172
Dir. of Survey
Downstream
Length Surveyed
353.1 ft.
Total Length
353.1 ft.
Structural Index
3
Structural Quick
3221
Structural Rating
8
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
3
Overall Quick
Overall Rating
8
Pipe schematic from manhole 01 1173 to 01 1172
MH: 01 1173MH: 01 1172downstream0 ft. AMH - Upstream Manhole, Survey Begins - 01 11730 ft. MWM - Water Mark, 25 %of cross sectional area0 ft. MWL - Water Level, 20 %of cross sectional area2.8 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start2.8 ft. MGO - General Observation - MAG COAT13.5 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"47 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"49.3 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"87.9 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"96.6 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"97.3 ft. TFA - Tap Factory Made Active, at 02 o'clock, -, within 8 inches of joint: NO, 6"115.3 ft. CL - Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Start122.4 ft. CL - Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Finish147.3 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"149.5 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"150.8 ft. CM - Crack Multiple, from 10 to 02 o'clock, within 8 inches of joint: YES183 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"185.7 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"231.8 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"234.5 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"288.5 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"290.9 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"337.4 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"339.8 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"353.1 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish353.1 ft. AMH - Downstream Manhole, Survey Ends - 01 1172

Observation photos (3)

  • Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    2.8 ft. - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Start

    115.3 ft. - Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Start

  • Crack Multiple, from 10 to 02 o'clock, within 8 inches of joint: YES

    150.8 ft. - Crack Multiple, from 10 to 02 o'clock, within 8 inches of joint: YES

Observations (26)

DistanceCodeObservation
353.1SAV
288.5TF
183TF
290.9TF
2.8SAV
231.8TF
149.5TF
234.5TF
0AMH01 1173
147.3TF
13.5TF
96.6TF
122.4CL
150.8CM
49.3TF
115.3CL
185.7TF
337.4TF
47TF
353.1AMH01 1172
0MWM
87.9TF
339.8TF
97.3TFA
0MWL
2.8MGOMAG COAT

Properties (6)

additional_info
SC411122
custom_field_two
3
customer
LACSD
datetime
2020-04-13T22:21:18-07:00
documentation
PROPIPE
is_lateral_inspection
false