Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Mar 20, 2020, 09:13 AM
  • 21 1012_21 1011 _03202020_023254.mp4

Date
03/20/2020
W/O
818333
Weather
Light Rain
Operator/Surveyor
N.ZAHREDDINE
Sewer ID
Z00784
PipeID
P16112
Time
2:13 AM
Certificate
U-109-7948
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
K7319
Sewer Name
21 SAN ANTONIO TRUNK
City
POMONA
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 21
Page No.
06
Purpose
Routine Assessment
Project
RFIR_WO_818333_TV21091_MAR2020
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
12 in.
Width
12 in.
Upstream MH
21 1012
Downstream MH
21 1011
Dir. of Survey
Downstream
Length Surveyed
349.7 ft.
Total Length
349.7 ft.
Structural Index
4
Structural Quick
4400
Structural Rating
16
O&M Index
2
O&M Quick
2100
O&M Rating
2
Overall Index
4
Overall Quick
Overall Rating
18
Pipe schematic from manhole 21 1012 to 21 1011
MH: 21 1012MH: 21 1011downstream0 ft. MWL - Water Level, 5 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 21 10120 ft. MWM - Water Mark, 25 %of cross sectional area2 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 05 to 07 o'clock, , within 8 inches of joint: YES, Start34.3 ft. FM - Fracture Multiple, from 03 to 05 o'clock, within 8 inches of joint: YES51.2 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"52.3 ft. FM - Fracture Multiple, from 10 to 01 o'clock, within 8 inches of joint: YES78.1 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"79.2 ft. FM - Fracture Multiple, from 09 to 02 o'clock, within 8 inches of joint: YES86.7 ft. FM - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start124.9 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 4"151.8 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 4"179.2 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 4"201.5 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 4"228.1 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 4"250.8 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 4"277.8 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 4"300.1 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 4"327.1 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 4"334 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 4"344.7 ft. FM - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish345.9 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 05 to 07 o'clock, , within 8 inches of joint: YES, Finish349.7 ft. AMH - Downstream Manhole, Survey Ends - 21 1011

Observation photos (4)

  • Fracture Multiple, from 03 to 05 o'clock, within 8 inches of joint: YES

    34.3 ft. - Fracture Multiple, from 03 to 05 o'clock, within 8 inches of joint: YES

  • Fracture Multiple, from 10 to 01 o'clock, within 8 inches of joint: YES

    52.3 ft. - Fracture Multiple, from 10 to 01 o'clock, within 8 inches of joint: YES

  • Fracture Multiple, from 09 to 02 o'clock, within 8 inches of joint: YES

    79.2 ft. - Fracture Multiple, from 09 to 02 o'clock, within 8 inches of joint: YES

  • Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    86.7 ft. - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

Observations (23)

DistanceCodeObservation
344.7FM
334TFC
51.2TFC
86.7FM
179.2TFC
345.9DAGS
124.9TFC
228.1TFC
277.8TFC
349.7AMH21 1011
79.2FM
34.3FM
0MWL
0AMH21 1012
52.3FM
0MWM
250.8TFC
300.1TFC
78.1TF
151.8TFC
201.5TFC
327.1TFC
2DAGS

Properties (6)

additional_info
SC366945
custom_field_two
3
customer
LACSD
datetime
2020-03-20T02:13:44-07:00
documentation
PRO PIPE
is_lateral_inspection
false