Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Mar 26, 2020, 08:45 AM
  • 21 0997_21 0996 _03262020_022448.mp4

Date
03/26/2020
W/O
818333
Weather
Dry
Operator/Surveyor
M.MARTINEZ
Sewer ID
Z00784
PipeID
P16097
Time
1:45 AM
Certificate
U-115-06022794
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
K7366
Sewer Name
21 SAN ANTONIO TRUNK
City
POMONA
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 21
Page No.
06
Purpose
Routine Assessment
Project
RFIR_WO_818333_TV21091_MAR2020
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
15 in.
Width
15 in.
Upstream MH
21 0996
Downstream MH
21 0997
Dir. of Survey
Upstream
Length Surveyed
361.3 ft.
Total Length
361.3 ft.
Structural Index
4
Structural Quick
4100
Structural Rating
4
O&M Index
2
O&M Quick
2A00
O&M Rating
20
Overall Index
2
Overall Quick
Overall Rating
24
Pipe schematic from manhole 21 0996 to 21 0997
MH: 21 0996MH: 21 0997upstream0 ft. MGO - General Observation - CONNECTION AT MH 9 OCLOCK0 ft. AMH - Upstream Manhole, Survey Ends - 21 09970 ft. MGO - General Observation - LATERAL AT MH 3 OCLOCK CAPPED1.4 ft. FM - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish41.2 ft. TBC - Tap Break-In Capped, at 01 o'clock, -, within 8 inches of joint: YES, 6"51.2 ft. TBC - Tap Break-In Capped, at 10 o'clock, -, within 8 inches of joint: YES, 6"82.2 ft. TBC - Tap Break-In Capped, at 01 o'clock, -, within 8 inches of joint: YES, 6"106.4 ft. TBC - Tap Break-In Capped, at 10 o'clock, -, within 8 inches of joint: YES, 6"130 ft. TBC - Tap Break-In Capped, at 01 o'clock, -, within 8 inches of joint: YES, 6"157.8 ft. TBC - Tap Break-In Capped, at 11 o'clock, -, within 8 inches of joint: YES, 6"179.6 ft. TBC - Tap Break-In Capped, at 01 o'clock, -, within 8 inches of joint: YES, 6"201.9 ft. TFC - Tap Factory Made Capped, at 11 o'clock, -, within 8 inches of joint: YES, 6"236.3 ft. TF - Tap Factory Made, at 01 o'clock, -, within 8 inches of joint: YES, 6"259.3 ft. TBC - Tap Break-In Capped, at 10 o'clock, -, within 8 inches of joint: YES, 6"287.2 ft. TBC - Tap Break-In Capped, at 11 o'clock, -, within 8 inches of joint: YES, 6"302 ft. TBC - Tap Break-In Capped, at 02 o'clock, -, within 8 inches of joint: YES, 6"336.7 ft. TB - Tap Break-In, at 11 o'clock, -, within 8 inches of joint: YES, 6"359.2 ft. FM - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start361.3 ft. AMH - Downstream Manhole, Survey Begins - 21 0996361.3 ft. MWM - Water Mark, 25 %of cross sectional area361.3 ft. MWL - Water Level, 20 %of cross sectional area

Observation photos (1)

  • Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    2.1 ft. - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

Observations (21)

DistanceCodeObservation
279.1TBC
2.1FM
0AMH21 0996
359.9FM
320.1TBC
361.3MGOCONNECTION AT MH 9 OCLOCK
361.3AMH21 0997
361.3MGOLATERAL AT MH 3 OCLOCK CAPPED
59.3TBC
0MWM
125TF
181.7TBC
159.4TFC
254.9TBC
102TBC
310.1TBC
24.6TB
231.3TBC
203.5TBC
74.1TBC
0MWL

Properties (5)

custom_field_two
3
customer
LACSD
datetime
2020-03-26T01:45:16-07:00
documentation
PRO PIPE
is_lateral_inspection
false