Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Mar 25, 2020, 07:38 AM
  • H 0203_H 0202 _03252020_004311.mp4

Date
03/25/2020
W/O
818416
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00169
PipeID
P11227
Time
12:38 AM
Certificate
U-508-7069
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K7491
Sewer Name
H JOINT OUTFALL H - UNIT 2C
City
BELL GARDENS
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 02
Page No.
20
Purpose
Routine Assessment
Project
RFIR_WO_818416_TV02368_MAR2020
Sewer Type
Gravity
Material
Reinforced Concrete Pipe
Shape
Circular
Height
36 in.
Width
36 in.
Upstream MH
H 0203
Downstream MH
H 0202
Dir. of Survey
Downstream
Length Surveyed
138.4 ft.
Total Length
138.4 ft.
Structural Index
3
Structural Quick
3D00
Structural Rating
81
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
3
Overall Quick
Overall Rating
81
Pipe schematic from manhole H 0203 to H 0202
MH: H 0203MH: H 0202downstream0 ft. MWM - Water Mark, 30 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - H 02030 ft. MWL - Water Level, 25 %of cross sectional area0.7 ft. MGO - General Observation - MAG COAT3.5 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start138 ft. MGO - General Observation - POSSIBLE REINFORCEMENT VISIBLE THROUGHOUT THE REACH138.4 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish138.4 ft. AMH - Downstream Manhole, Survey Ends - H 0202

Observation photos (1)

  • Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    3.5 ft. - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

Observations (8)

DistanceCodeObservation
0MWM
0AMHH 0203
138MGOPOSSIBLE REINFORCEMENT VISIBLE THROUGHOUT THE REACH
0MWL
138.4SAV
138.4AMHH 0202
0.7MGOMAG COAT
3.5SAV

Properties (6)

additional_info
SC398898
custom_field_two
3
customer
LACSD
datetime
2020-03-25T00:38:06-07:00
documentation
PROPIPE
is_lateral_inspection
false