Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Mar 25, 2020, 08:13 AM
  • H 0202_H 0201 _03252020_012706.mp4

Date
03/25/2020
W/O
818416
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00169
PipeID
P11226
Time
1:13 AM
Certificate
U-508-7069
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K7491
Sewer Name
H JOINT OUTFALL H - UNIT 2C
City
BELL GARDENS
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 02
Page No.
20
Purpose
Routine Assessment
Project
RFIR_WO_818416_TV02368_MAR2020
Sewer Type
Gravity
Material
Reinforced Concrete Pipe
Shape
Circular
Height
36 in.
Width
36 in.
Upstream MH
H 0202
Downstream MH
H 0201
Dir. of Survey
Downstream
Length Surveyed
440.6 ft.
Total Length
440.6 ft.
Structural Index
3
Structural Quick
3P00
Structural Rating
261
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
3
Overall Quick
Overall Rating
261
Pipe schematic from manhole H 0202 to H 0201
MH: H 0202MH: H 0201downstream0 ft. MWM - Water Mark, 35 %of cross sectional area0 ft. MWL - Water Level, 25 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - H 02024.6 ft. MGO - General Observation - MAG COAT4.6 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start440 ft. MGO - General Observation - POSSIBLE REINFORCEMENT VISIBLE THROUGHOUT THE REACH440.6 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish440.6 ft. AMH - Downstream Manhole, Survey Ends - H 0201

Observation photos (1)

  • Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    4.6 ft. - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

Observations (8)

DistanceCodeObservation
0MWM
440.6SAV
4.6MGOMAG COAT
0MWL
0AMHH 0202
4.6SAV
440MGOPOSSIBLE REINFORCEMENT VISIBLE THROUGHOUT THE REACH
440.6AMHH 0201

Properties (6)

additional_info
SC398898
custom_field_two
3
customer
LACSD
datetime
2020-03-25T01:13:32-07:00
documentation
PROPIPE
is_lateral_inspection
false