Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Mar 25, 2020, 09:32 AM
  • H 0200_H 0199 _03252020_024414.mp4

Date
03/25/2020
W/O
818416
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00169
PipeID
P11224
Time
2:32 AM
Certificate
U-508-7069
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K7491
Sewer Name
H JOINT OUTFALL H - UNIT 2C
City
BELL GARDENS
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 02
Page No.
23
Purpose
Routine Assessment
Project
RFIR_WO_818416_TV02368_MAR2020
Sewer Type
Gravity
Material
Reinforced Concrete Pipe
Shape
Circular
Height
36 in.
Width
36 in.
Upstream MH
H 0200
Downstream MH
H 0199
Dir. of Survey
Downstream
Length Surveyed
455.5 ft.
Total Length
455.5 ft.
Structural Index
3
Structural Quick
3Q00
Structural Rating
270
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
3
Overall Quick
Overall Rating
270
Pipe schematic from manhole H 0200 to H 0199
MH: H 0200MH: H 0199downstream0 ft. AMH - Upstream Manhole, Survey Begins - H 02000 ft. MWL - Water Level, 20 %of cross sectional area0 ft. MWM - Water Mark, 30 %of cross sectional area2.9 ft. MGO - General Observation - MAG COAT3.6 ft. SAP - Surface Aggregate Projecting, from 07 to 05 o'clock, within 8 inches of joint: YES, Start455 ft. MGO - General Observation - POSSIBLE REINFORCEMENT VISIBLE THROUGHOUT THE REACH455.5 ft. AMH - Downstream Manhole, Survey Ends - H 0199455.5 ft. SAP - Surface Aggregate Projecting, from 07 to 05 o'clock, within 8 inches of joint: YES, Finish

Observation photos (1)

  • Surface Aggregate Projecting, from 07 to 05 o'clock, within 8 inches of joint: YES, Start

    3.6 ft. - Surface Aggregate Projecting, from 07 to 05 o'clock, within 8 inches of joint: YES, Start

Observations (8)

DistanceCodeObservation
455MGOPOSSIBLE REINFORCEMENT VISIBLE THROUGHOUT THE REACH
3.6SAP
0AMHH 0200
0MWL
455.5AMHH 0199
0MWM
2.9MGOMAG COAT
455.5SAP

Properties (6)

additional_info
SC398898
custom_field_two
2
customer
LACSD
datetime
2020-03-25T02:32:56-07:00
documentation
PROPIPE
is_lateral_inspection
false