Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Mar 26, 2020, 04:28 AM
  • H 0199_H 0198 _03252020_213643.mp4

Date
03/25/2020
W/O
818416
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00169
PipeID
P11223
Time
9:28 PM
Certificate
U-508-7069
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K7492
Sewer Name
H JOINT OUTFALL H - UNIT 2C
City
BELL GARDENS
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 02
Page No.
23
Purpose
Routine Assessment
Project
RFIR_WO_818416_TV02368_MAR2020
Sewer Type
Gravity
Material
Reinforced Concrete Pipe
Shape
Circular
Height
36 in.
Width
36 in.
Upstream MH
H 0199
Downstream MH
H 0198
Dir. of Survey
Downstream
Length Surveyed
246.6 ft.
Total Length
246.7 ft.
Structural Index
3
Structural Quick
3I00
Structural Rating
144
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
3
Overall Quick
Overall Rating
144
Pipe schematic from manhole H 0199 to H 0198
MH: H 0199MH: H 0198downstream0 ft. MWM - Water Mark, 35 %of cross sectional area0 ft. MWL - Water Level, 30 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - H 01992.7 ft. MGO - General Observation - MAG COAT2.8 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start243 ft. MGO - General Observation - POSSIBLE REINFORCEMENT VISIBLE THROUGHOUT THE REACH243.5 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish246.7 ft. AMH - Downstream Manhole, Survey Ends - H 0198

Observation photos (1)

  • Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    2.8 ft. - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

Observations (8)

DistanceCodeObservation
243MGOPOSSIBLE REINFORCEMENT VISIBLE THROUGHOUT THE REACH
2.8SAP
243.5SAP
0MWM
0MWL
2.7MGOMAG COAT
246.7AMHH 0198
0AMHH 0199

Properties (6)

additional_info
SC398899
custom_field_two
2
customer
LACSD
datetime
2020-03-25T21:28:14-07:00
documentation
PROPIPE
is_lateral_inspection
false