Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Mar 26, 2020, 06:09 AM
  • H 0196_H 0195 _03262020_003727.mp4

Date
03/25/2020
W/O
818416
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00169
PipeID
P11220
Time
11:09 PM
Certificate
U-508-7069
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K7492
Sewer Name
H JOINT OUTFALL H - UNIT 2C
City
BELL GARDENS
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 02
Page No.
23
Purpose
Routine Assessment
Project
RFIR_WO_818416_TV02368_MAR2020
Sewer Type
Gravity
Material
Reinforced Concrete Pipe
Shape
Circular
Height
36 in.
Width
36 in.
Upstream MH
H 0196
Downstream MH
H 0195
Dir. of Survey
Downstream
Length Surveyed
445.1 ft.
Total Length
445.1 ft.
Structural Index
3
Structural Quick
3Q00
Structural Rating
267
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
3
Overall Quick
Overall Rating
267
Pipe schematic from manhole H 0196 to H 0195
MH: H 0196MH: H 0195downstream0 ft. MWM - Water Mark, 35 %of cross sectional area0 ft. MWL - Water Level, 30 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - H 01962.2 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start2.2 ft. MGO - General Observation - MAG COAT445 ft. MGO - General Observation - POSSIBLE REINFORCEMENT VISIBLE THROUGHOUT THE REACH445.1 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish445.1 ft. AMH - Downstream Manhole, Survey Ends - H 0195

Observation photos (1)

  • Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    2.2 ft. - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

Observations (8)

DistanceCodeObservation
2.2SAP
0MWM
2.2MGOMAG COAT
0MWL
445.1SAP
445.1AMHH 0195
445MGOPOSSIBLE REINFORCEMENT VISIBLE THROUGHOUT THE REACH
0AMHH 0196

Properties (6)

additional_info
SC398899
custom_field_two
2
customer
LACSD
datetime
2020-03-25T23:09:54-07:00
documentation
PROPIPE
is_lateral_inspection
false