Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Apr 9, 2020, 06:02 AM
  • 05 1604_05 1603_04082020_231107.mp4

Date
04/08/2020
W/O
818453
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00551
PipeID
P06828
Time
11:02 PM
Certificate
U-508-7069
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K7558
Sewer Name
05 203RD STREET TRUNK
City
TORRANCE
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 05
Page No.
27
Purpose
Routine Assessment
Project
RFIR_WO_818453_TV05176_MAR2020
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
24 in.
Width
24 in.
Upstream MH
05 1604
Downstream MH
05 1603
Dir. of Survey
Downstream
Length Surveyed
298.9 ft.
Total Length
298.9 ft.
Structural Index
4
Structural Quick
4K00
Structural Rating
236
O&M Index
2
O&M Quick
2K00
O&M Rating
118
Overall Index
3
Overall Quick
Overall Rating
354
Pipe schematic from manhole 05 1604 to 05 1603
MH: 05 1604MH: 05 1603downstream0 ft. MWM - Water Mark, 10 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 05 16040 ft. MWL - Water Level, 5 %of cross sectional area2 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 05 to 07 o'clock, , within 8 inches of joint: YES, Start5.2 ft. FM - Fracture Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES, Start5.3 ft. IS - Infiltration Stain, from 08 to 04 o'clock, within 8 inches of joint: YES, Start23 ft. TF - Tap Factory Made, at 12 o'clock, -, within 8 inches of joint: NO, 6" - OPEN60.3 ft. TF - Tap Factory Made, at 12 o'clock, -, within 8 inches of joint: NO, 6" - OPEN113.2 ft. TBA - Tap Break-In Active, at 12 o'clock, -, within 8 inches of joint: NO, 6"273.6 ft. TF - Tap Factory Made, at 12 o'clock, -, within 8 inches of joint: NO, 6" - OPEN296 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 05 to 07 o'clock, , within 8 inches of joint: YES, Finish298.7 ft. IS - Infiltration Stain, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish298.9 ft. FM - Fracture Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES, Finish298.9 ft. AMH - Downstream Manhole, Survey Ends - 05 1603

Observation photos (3)

  • Fracture Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

    5.2 ft. - Fracture Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

  • Infiltration Stain, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    5.3 ft. - Infiltration Stain, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Tap Break-In Active, at 12 o'clock, -, within 8 inches of joint: NO, 6"

    113.2 ft. - Tap Break-In Active, at 12 o'clock, -, within 8 inches of joint: NO, 6"

Observations (14)

DistanceCodeObservation
2DAGS
298.9FM
0MWM
273.6TFOPEN
298.7IS
0AMH05 1604
296DAGS
60.3TFOPEN
298.9AMH05 1603
5.3IS
23TFOPEN
5.2FM
0MWL
113.2TBA

Properties (6)

additional_info
SC411117
custom_field_two
2
customer
LACSD
datetime
2020-04-08T23:02:11-07:00
documentation
PROPIPE
is_lateral_inspection
false