Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Mar 31, 2020, 04:23 AM
  • 01 0541_01 0540_03302020_214504.mp4

Date
03/30/2020
W/O
818429
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00206
PipeID
P01029
Time
9:23 PM
Certificate
U-508-7069
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K7494
Sewer Name
01 CROCKETT BOULEVARD-GLEN AVENUE TRUNK
City
LOS ANGELES
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 01
Page No.
10
Purpose
Routine Assessment
Project
RFIR_WO_818429_TV01232_MAR2020
Sewer Type
Gravity
Material
NRCP
Shape
Circular
Height
12 in.
Width
12 in.
Upstream MH
01 0541
Downstream MH
01 0540
Dir. of Survey
Downstream
Length Surveyed
321.8 ft.
Total Length
321.8 ft.
Structural Index
3
Structural Quick
4134
Structural Rating
20
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
3
Overall Quick
Overall Rating
20
Pipe schematic from manhole 01 0541 to 01 0540
MH: 01 0541MH: 01 0540downstream0 ft. AMH - Upstream Manhole, Survey Begins - 01 05410 ft. MWM - Water Mark, 25 %of cross sectional area0 ft. MWL - Water Level, 20 %of cross sectional area3.1 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start28.4 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6" - ACTIVE69.7 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"72.2 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"91.4 ft. CM - Crack Multiple, from 09 to 01 o'clock, within 8 inches of joint: YES121.5 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"122.2 ft. CL - Crack Longitudinal, at 02 o'clock, within 8 inches of joint: YES164.9 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"167.7 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"189.4 ft. CL - Crack Longitudinal, at 10 o'clock, within 8 inches of joint: YES190.8 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"252.4 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"272.8 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"301.3 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES303 ft. TB - Tap Break-In, at 02 o'clock, -, within 8 inches of joint: NO, 6"306.4 ft. CM - Crack Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES314 ft. FM - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES315.7 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"321.8 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish321.8 ft. AMH - Downstream Manhole, Survey Ends - 01 0540

Observation photos (8)

  • Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    3.1 ft. - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Crack Multiple, from 09 to 01 o'clock, within 8 inches of joint: YES

    91.4 ft. - Crack Multiple, from 09 to 01 o'clock, within 8 inches of joint: YES

  • Crack Longitudinal, at 02 o'clock, within 8 inches of joint: YES

    122.2 ft. - Crack Longitudinal, at 02 o'clock, within 8 inches of joint: YES

  • Crack Longitudinal, at 10 o'clock, within 8 inches of joint: YES

    189.4 ft. - Crack Longitudinal, at 10 o'clock, within 8 inches of joint: YES

  • Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES

    301.3 ft. - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES

  • Tap Break-In, at 02 o'clock, -, within 8 inches of joint: NO, 6"

    303 ft. - Tap Break-In, at 02 o'clock, -, within 8 inches of joint: NO, 6"

  • Crack Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES

    306.4 ft. - Crack Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES

  • Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES

    314 ft. - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES

Observations (23)

DistanceCodeObservation
252.4TFC
189.4CL
167.7TF
28.4TFACTIVE
190.8TF
0AMH01 0541
306.4CM
314FM
122.2CL
303TB
121.5TF
321.8SAV
321.8AMH01 0540
72.2TFC
164.9TFC
69.7TF
315.7TF
272.8TF
0MWM
301.3CM
3.1SAV
0MWL
91.4CM

Properties (6)

additional_info
SC411101
custom_field_two
3
customer
LACSD
datetime
2020-03-30T21:23:44-07:00
documentation
PROPIPE
is_lateral_inspection
false