Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Mar 31, 2020, 05:00 AM
  • 01 0539_01 0538A_03302020_221526.mp4

Date
03/30/2020
W/O
818429
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00206
PipeID
P01027
Time
10:00 PM
Certificate
U-508-7069
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K7494
Sewer Name
01 CROCKETT BOULEVARD-GLEN AVENUE TRUNK
City
LOS ANGELES
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 01
Page No.
10
Purpose
Routine Assessment
Project
RFIR_WO_818429_TV01232_MAR2020
Sewer Type
Gravity
Material
NRCP
Shape
Circular
Height
12 in.
Width
12 in.
Upstream MH
01 0539
Downstream MH
01 0538A
Dir. of Survey
Downstream
Length Surveyed
249.4 ft.
Total Length
249.4 ft.
Structural Index
3
Structural Quick
3221
Structural Rating
8
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
3
Overall Quick
Overall Rating
8
Pipe schematic from manhole 01 0539 to 01 0538A
MH: 01 0539MH: 01 0538Adownstream0 ft. MWM - Water Mark, 25 %of cross sectional area0 ft. MWL - Water Level, 20 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 01 05392.8 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start2.8 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start15.2 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"40.4 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"53.2 ft. SSS - Surface Spalling, from 01 to 05 o'clock, within 8 inches of joint: NO65.8 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"78.7 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"96.6 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"129.6 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"138.5 ft. RPZ - Repair Other, within 8 inches of joint: YES162.3 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"164.8 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"200.6 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6" - OPEN - UNKNOWN ACTIVITY STATUS (DEBRIS PRESENT)239.5 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"242 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"249.4 ft. AMH - Downstream Manhole, Survey Ends - 01 0538A249.4 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish249.4 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish249.4 ft. MGO - General Observation - ACTIVE CONNECTION AT MH 9 O'CLOCK

Observation photos (4)

  • Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    2.8 ft. - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    2.8 ft. - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Surface Spalling, from 01 to 05 o'clock, within 8 inches of joint: NO

    53.2 ft. - Surface Spalling, from 01 to 05 o'clock, within 8 inches of joint: NO

  • Repair Other, within 8 inches of joint: YES

    138.5 ft. - Repair Other, within 8 inches of joint: YES

Observations (22)

DistanceCodeObservation
242TF
249.4AMH01 0538A
138.5RPZ
2.8SAV
2.8CM
15.2TF
164.8TF
249.4SAV
40.4TFC
65.8TF
0MWM
200.6TFOPEN - UNKNOWN ACTIVITY STATUS (DEBRIS PRESENT)
162.3TFC
0MWL
249.4CM
78.7TFC
53.2SSS
96.6TFC
0AMH01 0539
129.6TF
239.5TFC
249.4MGOACTIVE CONNECTION AT MH 9 O'CLOCK

Properties (6)

additional_info
SC411101
custom_field_two
3
customer
LACSD
datetime
2020-03-30T22:00:37-07:00
documentation
PROPIPE
is_lateral_inspection
false