Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Apr 9, 2020, 08:57 AM
  • 05 2312_05 2311 _04092020_020413.mp4

Date
04/09/2020
W/O
818386
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00462
PipeID
P07434
Time
1:57 AM
Certificate
U-508-7069
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K7560
Sewer Name
05 INGLEWOOD TRUNK #1 RELIEF
City
INGLEWOOD
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 05
Page No.
03
Purpose
Routine Assessment
Project
RFIR_WO_818386_TV05349_MAR2020
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
15 in.
Width
15 in.
Upstream MH
05 2312
Downstream MH
05 2311
Dir. of Survey
Downstream
Length Surveyed
166.9 ft.
Total Length
166.9 ft.
Structural Index
2
Structural Quick
2F00
Structural Rating
66
O&M Index
2
O&M Quick
2E11
O&M Rating
65
Overall Index
2
Overall Quick
Overall Rating
131
Pipe schematic from manhole 05 2312 to 05 2311
MH: 05 2312MH: 05 2311downstream0 ft. AMH - Upstream Manhole, Survey Begins - 05 23120 ft. VC - Vermin Cockroach, within 8 inches of joint: NO - @ MH0 ft. MWM - Water Mark, 15 %of cross sectional area0 ft. MWL - Water Level, 10 %of cross sectional area2 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start2 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start109.6 ft. FC - Fracture Circumferential, from 03 to 05 o'clock, within 8 inches of joint: YES164 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish164 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish166.9 ft. AMH - Downstream Manhole, Survey Ends - 05 2311

Observation photos (1)

  • Fracture Circumferential, from 03 to 05 o'clock, within 8 inches of joint: YES

    109.6 ft. - Fracture Circumferential, from 03 to 05 o'clock, within 8 inches of joint: YES

Observations (10)

DistanceCodeObservation
164SSS
0AMH05 2312
2SSS
0VC@ MH
0MWM
164DAGS
0MWL
109.6FC
2DAGS
166.9AMH05 2311

Properties (7)

additional_info
SC411119
custom_field_two
3
customer
LACSD
datetime
2020-04-09T01:57:02-07:00
documentation
PROPIPE
is_lateral_inspection
false
year_laid
30643