- Date
- 04/07/2020
- W/O
- 818432
- Weather
- Dry
- Operator/Surveyor
- B.FUGATE
- Sewer ID
- Z00523
- PipeID
- P05932
- Time
- 3:36 AM
- Certificate
- U-508-7069
- System Owner
- LACSD
- Date Cleaned
- —
- Pre-Cleaning
- No Pre-Cleaning
- Media Label
- K7555
- Sewer Name
- 05 SOUTH INGLEWOOD-ORANGE AVENUE TRUNK, EXTENSION #2
- City
- INGLEWOOD
- Loc. details
- Light Highway
- Location Code
- C
- Use of Sewer
- Sanitary Sewer
- District
- District 05
- Page No.
- 07
- Purpose
- Routine Assessment
- Project
- RFIR_WO_818432_TV05208_MAR2020
- Sewer Type
- Gravity
- Material
- Vitrified Clay Pipe
- Shape
- Circular
- Height
- 8 in.
- Width
- 8 in.
- Upstream MH
- 05 0700
- Downstream MH
- 05 0699
- Dir. of Survey
- Downstream
- Length Surveyed
- 265.8 ft.
- Total Length
- 265.8 ft.
- Structural Index
- 3
- Structural Quick
- 3100
- Structural Rating
- 3
- O&M Index
- 0
- O&M Quick
- 0000
- O&M Rating
- 0
- Overall Index
- 3
- Overall Quick
- —
- Overall Rating
- 3
Pipe schematic from manhole 05 0700 to 05 0699 Observation photos (3)

6.1 ft. - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

103.6 ft. - Surface Other, at 10 o'clock, within 8 inches of joint: NO - hole

105.7 ft. - Tap Break-In, at 10 o'clock, -, within 8 inches of joint: NO, 6" - ACTIVE