Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Apr 7, 2020, 10:36 AM
  • 05 0700_05 0699 _04072020_034947.mp4

Date
04/07/2020
W/O
818432
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00523
PipeID
P05932
Time
3:36 AM
Certificate
U-508-7069
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K7555
Sewer Name
05 SOUTH INGLEWOOD-ORANGE AVENUE TRUNK, EXTENSION #2
City
INGLEWOOD
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 05
Page No.
07
Purpose
Routine Assessment
Project
RFIR_WO_818432_TV05208_MAR2020
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
8 in.
Width
8 in.
Upstream MH
05 0700
Downstream MH
05 0699
Dir. of Survey
Downstream
Length Surveyed
265.8 ft.
Total Length
265.8 ft.
Structural Index
3
Structural Quick
3100
Structural Rating
3
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
3
Overall Quick
Overall Rating
3
Pipe schematic from manhole 05 0700 to 05 0699
MH: 05 0700MH: 05 0699downstream0 ft. AMH - Upstream Manhole, Survey Begins - 05 07000 ft. MWL - Water Level, 10 %of cross sectional area0.7 ft. MWM - Water Mark, 20 %of cross sectional area6.1 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start53.4 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"101.9 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"103.6 ft. SZ - Surface Other, at 10 o'clock, within 8 inches of joint: NO - hole105.7 ft. TB - Tap Break-In, at 10 o'clock, -, within 8 inches of joint: NO, 6" - ACTIVE154.2 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"204.8 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"253.5 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"265.8 ft. AMH - Downstream Manhole, Survey Ends - 05 0699265.8 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish

Observation photos (3)

  • Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    6.1 ft. - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Surface Other, at 10 o'clock, within 8 inches of joint: NO - hole

    103.6 ft. - Surface Other, at 10 o'clock, within 8 inches of joint: NO - hole

  • Tap Break-In, at 10 o'clock, -, within 8 inches of joint: NO, 6" - ACTIVE

    105.7 ft. - Tap Break-In, at 10 o'clock, -, within 8 inches of joint: NO, 6" - ACTIVE

Observations (13)

DistanceCodeObservation
6.1CM
265.8AMH05 0699
101.9TFC
0AMH05 0700
204.8TFC
103.6SZhole
105.7TBACTIVE
0.7MWM
265.8CM
53.4TF
253.5TFC
154.2TFC
0MWL

Properties (6)

additional_info
SC411114
custom_field_two
1
customer
LACSD
datetime
2020-04-07T03:36:23-07:00
documentation
PROPIPE
is_lateral_inspection
false