Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Apr 7, 2020, 08:53 AM
  • 18 0403_18 0402 _04072020_020459.mp4

Date
04/07/2020
W/O
818454
Weather
Light Rain
Operator/Surveyor
S. LOPEZ
Sewer ID
Z00699
PipeID
P14238
Time
1:53 AM
Certificate
U-111-11880
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K7514
Sewer Name
18 SANTA FE STREET RELIEF TRUNK
City
WHITTIER
Loc. details
Easement/Right of Way
Location Code
D
Use of Sewer
Sanitary Sewer
District
District 18
Page No.
21
Purpose
Routine Assessment
Project
RFIR_WO_818454_TV18173_MAR2020
Sewer Type
Gravity
Material
NRCP
Shape
Circular
Height
15 in.
Width
15 in.
Upstream MH
18 0403
Downstream MH
18 0402
Dir. of Survey
Downstream
Length Surveyed
302.3 ft.
Total Length
302.3 ft.
Structural Index
3
Structural Quick
3K2K
Structural Rating
300
O&M Index
2
O&M Quick
412K
O&M Rating
124
Overall Index
2
Overall Quick
Overall Rating
424
Pipe schematic from manhole 18 0403 to 18 0402
MH: 18 0403MH: 18 0402downstream0 ft. MGO - General Observation - COCKROACHES IN MANHOLE0 ft. MWM - Water Mark, 25 %of cross sectional area0 ft. MWL - Water Level, 20 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 18 04032 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Start2 ft. SAP - Surface Aggregate Projecting, from 09 to 03 o'clock, within 8 inches of joint: YES, Start2 ft. SSS - Surface Spalling, from 09 to 03 o'clock, within 8 inches of joint: YES, Start290.1 ft. MGO - General Observation - ABANDONED MH300.4 ft. SSS - Surface Spalling, from 09 to 03 o'clock, within 8 inches of joint: YES, Finish300.4 ft. SAP - Surface Aggregate Projecting, from 09 to 03 o'clock, within 8 inches of joint: YES, Finish300.4 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Finish302.3 ft. MGO - General Observation - COCKROACHES IN MANHOLE302.3 ft. AMH - Downstream Manhole, Survey Ends - 18 0402

Observation photos (6)

  • General Observation - COCKROACHES IN MANHOLE

    0 ft. - General Observation - COCKROACHES IN MANHOLE

  • Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock,  , within 8 inches of joint: YES, Start

    2 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Start

  • Surface Aggregate Projecting, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

    2 ft. - Surface Aggregate Projecting, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

  • Surface Spalling, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

    2 ft. - Surface Spalling, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

  • General Observation - ABANDONED MH

    290.1 ft. - General Observation - ABANDONED MH

  • General Observation - COCKROACHES IN MANHOLE

    302.3 ft. - General Observation - COCKROACHES IN MANHOLE

Observations (13)

DistanceCodeObservation
302.3MGOCOCKROACHES IN MANHOLE
300.4SSS
0MGOCOCKROACHES IN MANHOLE
300.4SAP
300.4DAGS
0MWM
290.1MGOABANDONED MH
302.3AMH18 0402
2DAGS
2SAP
2SSS
0MWL
0AMH18 0403

Properties (6)

additional_info
SC411203
custom_field_two
3
customer
LACSD
datetime
2020-04-07T01:53:06-07:00
documentation
PRO PIPE
is_lateral_inspection
false