- Date
- 03/30/2020
- W/O
- 818426
- Weather
- Dry
- Operator/Surveyor
- M.MARTINEZ
- Sewer ID
- Z00784
- PipeID
- P16081
- Time
- 3:05 AM
- Certificate
- U-115-06022794
- System Owner
- LACSD
- Date Cleaned
- —
- Pre-Cleaning
- Not Known
- Media Label
- K7367
- Sewer Name
- 21 SAN ANTONIO TRUNK
- City
- POMONA
- Loc. details
- Light Highway
- Location Code
- C
- Use of Sewer
- Sanitary Sewer
- District
- District 21
- Page No.
- 09
- Purpose
- Routine Assessment
- Project
- RFIR_WO_818426_TV21055_MAR2020
- Sewer Type
- Gravity
- Material
- Reinforced Concrete Pipe
- Shape
- Circular
- Height
- 24 in.
- Width
- 24 in.
- Upstream MH
- 21 0981
- Downstream MH
- 21 0980
- Dir. of Survey
- Downstream
- Length Surveyed
- 376.4 ft.
- Total Length
- 376.4 ft.
- Structural Index
- 4
- Structural Quick
- 5U3N
- Structural Rating
- 919
- O&M Index
- 2
- O&M Quick
- 412N
- O&M Rating
- 153
- Overall Index
- 3
- Overall Quick
- —
- Overall Rating
- 1072
Pipe schematic from manhole 21 0981 to 21 0980 Observation photos (5)

2 ft. - Deposits Attached Grease, 10 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Start

8 ft. - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

18 ft. - Surface Reinforcement Visible, from 08 to 04 o'clock, within 8 inches of joint: YES

25.5 ft. - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

105.1 ft. - Surface Reinforcement Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start