Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Apr 28, 2020, 09:15 AM
  • 05 1490_05 1489_4282020_034322.mp4

Date
04/28/2020
W/O
0828780
Weather
Dry
Operator/Surveyor
REVELES
Sewer ID
Z00438
PipeID
P06716
Time
2:15 AM
Certificate
U-115-06022630
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
H1408
Sewer Name
05 EL NIDO TRUNK
City
TORRANCE
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 05
Page No.
22
Purpose
Routine Assessment
Project
20200428VMR_EL_NIDO_TRUNK
Material
NRCP
Shape
Circular
Height
12 in.
Upstream MH
05 1490
Downstream MH
05 1489
Dir. of Survey
Downstream
Length Surveyed
357.3 ft.
Total Length
357.3 ft.
Structural Index
3
Structural Quick
3121
Structural Rating
5
O&M Index
2
O&M Quick
3122
O&M Rating
7
Overall Index
2
Overall Quick
Overall Rating
12
Pipe schematic from manhole 05 1490 to 05 1489
MH: 05 1490MH: 05 1489downstream0 ft. MWM - Water Mark, 40 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 03:47 AM0 ft. MWL - Water Level, 15 %of cross sectional area2.3 ft. SAV - Surface Aggregate Visible, from 09 to 03 o'clock, within 8 inches of joint: YES, Start2.3 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 07 to 08 o'clock, , within 8 inches of joint: YES, Start2.3 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 05 o'clock, , within 8 inches of joint: YES, Start2.3 ft. SSS - Surface Spalling, from 09 to 03 o'clock, within 8 inches of joint: YES, Start18.4 ft. TFC - Tap Factory Made Capped, at 12 o'clock, -, within 8 inches of joint: YES, 4"122 ft. TFC - Tap Factory Made Capped, at 12 o'clock, -, within 8 inches of joint: YES, 4"262 ft. TFC - Tap Factory Made Capped, at 12 o'clock, -, within 8 inches of joint: YES, 4"310.8 ft. TFC - Tap Factory Made Capped, at 12 o'clock, -, within 8 inches of joint: YES, 4"357.3 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 05 o'clock, , within 8 inches of joint: YES, Finish357.3 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 07 to 08 o'clock, , within 8 inches of joint: YES, Finish357.3 ft. DAZ - Deposits Attached Other, 15 %of cross sectional area, from 04 to 05 o'clock, , within 8 inches of joint: YES - STICK357.3 ft. AMH - Downstream Manhole, Survey Ends - 04:20 AM357.3 ft. SSS - Surface Spalling, from 09 to 03 o'clock, within 8 inches of joint: YES, Finish357.3 ft. SAV - Surface Aggregate Visible, from 09 to 03 o'clock, within 8 inches of joint: YES, Finish

Observation photos (1)

  • Deposits Attached Other, 15 %of cross sectional area, from 04 to 05 o'clock,  , within 8 inches of joint: YES - STICK

    357.3 ft. - Deposits Attached Other, 15 %of cross sectional area, from 04 to 05 o'clock, , within 8 inches of joint: YES - STICK

Observations (17)

DistanceCodeObservation
357.3DAGS
0MWM
122TFC
357.3DAGS
262TFC
2.3SAV
0AMH03:47 AM
2.3DAGS
357.3DAZSTICK
357.3AMH04:20 AM
2.3DAGS
310.8TFC
357.3SSS
18.4TFC
2.3SSS
357.3SAV
0MWL

Properties (5)

custom_field_two
3
customer
LACSD
datetime
2020-04-28T02:15:08-07:00
documentation
REVELES, OLIVER III, CASTILLO, SKINNER
is_lateral_inspection
false