Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Apr 28, 2020, 08:06 AM
  • 08 1637_08 0136_4282020_010821.mp4

Date
04/28/2020
W/O
0823968
Weather
Dry
Operator/Surveyor
REVELES
Sewer ID
Z00539
PipeID
P06860
Time
1:06 AM
Certificate
U-115-06022630
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
H1406
Sewer Name
05 WEST TORRANCE TRUNK
City
TORRANCE
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 08
Page No.
13
Purpose
Routine Assessment
Project
20200428VMR_WEST_TORRANCE_TRUNK
Material
Vitrified Clay Pipe
Shape
Circular
Height
15 in.
Upstream MH
08 1637
Downstream MH
08 0136
Dir. of Survey
Downstream
Length Surveyed
161 ft.
Total Length
161 ft.
Structural Index
1
Structural Quick
3422
Structural Rating
36
O&M Index
2
O&M Quick
2200
O&M Rating
4
Overall Index
1
Overall Quick
Overall Rating
40
Pipe schematic from manhole 08 1637 to 08 0136
MH: 08 1637MH: 08 0136downstream0 ft. MWM - Water Mark, 40 %of cross sectional area0 ft. MWL - Water Level, 20 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 01:08 AM1.7 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 08 to 09 o'clock, , within 8 inches of joint: YES, Start1.7 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 04 o'clock, , within 8 inches of joint: YES, Start3.4 ft. CC - Crack Circumferential, from 03 to 04 o'clock, within 8 inches of joint: YES19.1 ft. CC - Crack Circumferential, from 10 to 11 o'clock, within 8 inches of joint: YES28.1 ft. CC - Crack Circumferential, from 10 to 02 o'clock, within 8 inches of joint: YES30.8 ft. CC - Crack Circumferential, from 11 to 02 o'clock, within 8 inches of joint: YES33.9 ft. CC - Crack Circumferential, from 09 to 11 o'clock, within 8 inches of joint: YES36.7 ft. CC - Crack Circumferential, from 12 to 03 o'clock, within 8 inches of joint: YES40.3 ft. TFA - Tap Factory Made Active, at 12 o'clock, -, within 8 inches of joint: YES, 4"42.9 ft. CC - Crack Circumferential, from 10 to 01 o'clock, within 8 inches of joint: YES48.9 ft. CM - Crack Multiple, from 10 to 01 o'clock, within 8 inches of joint: YES55 ft. CC - Crack Circumferential, from 11 to 02 o'clock, within 8 inches of joint: YES60.7 ft. CM - Crack Multiple, from 11 to 02 o'clock, within 8 inches of joint: YES67 ft. CC - Crack Circumferential, from 11 to 02 o'clock, within 8 inches of joint: YES70.1 ft. CC - Crack Circumferential, from 09 to 03 o'clock, within 8 inches of joint: YES76.2 ft. CM - Crack Multiple, from 10 to 02 o'clock, within 8 inches of joint: YES79.2 ft. CC - Crack Circumferential, from 11 to 02 o'clock, within 8 inches of joint: YES86.1 ft. TFC - Tap Factory Made Capped, at 12 o'clock, -, within 8 inches of joint: YES, 4"91.4 ft. CC - Crack Circumferential, from 11 to 01 o'clock, within 8 inches of joint: YES98 ft. CC - Crack Circumferential, from 08 to 09 o'clock, within 8 inches of joint: YES103.7 ft. CC - Crack Circumferential, from 11 to 01 o'clock, within 8 inches of joint: YES112.9 ft. CC - Crack Circumferential, from 11 to 01 o'clock, within 8 inches of joint: YES118.8 ft. CC - Crack Circumferential, from 11 to 12 o'clock, within 8 inches of joint: YES122 ft. CC - Crack Circumferential, from 10 to 01 o'clock, within 8 inches of joint: YES137.3 ft. CC - Crack Circumferential, from 11 to 01 o'clock, within 8 inches of joint: YES150 ft. CC - Crack Circumferential, from 11 to 01 o'clock, within 8 inches of joint: YES152.7 ft. CM - Crack Multiple, from 09 to 02 o'clock, within 8 inches of joint: YES159 ft. FC - Fracture Circumferential, from 08 to 09 o'clock, within 8 inches of joint: YES159 ft. CL - Crack Longitudinal, at 11 o'clock, within 8 inches of joint: YES160.1 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 04 o'clock, , within 8 inches of joint: YES, Finish160.1 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 08 to 09 o'clock, , within 8 inches of joint: YES, Finish160.6 ft. CC - Crack Circumferential, from 10 to 02 o'clock, within 8 inches of joint: YES161 ft. AMH - Downstream Manhole, Survey Ends - 01:48 AM

Observations (36)

DistanceCodeObservation
86.1TFC
159FC
33.9CC
40.3TFA
48.9CM
0MWM
36.7CC
76.2CM
91.4CC
60.7CM
98CC
19.1CC
30.8CC
152.7CM
3.4CC
160.1DAGS
112.9CC
67CC
0MWL
160.6CC
161AMH01:48 AM
160.1DAGS
42.9CC
79.2CC
0AMH01:08 AM
103.7CC
55CC
137.3CC
150CC
1.7DAGS
1.7DAGS
122CC
70.1CC
159CL
118.8CC
28.1CC

Properties (5)

custom_field_two
3
customer
LACSD
datetime
2020-04-28T01:06:00-07:00
documentation
REVELES, OLIVER III, CASTILLO, SKINNER
is_lateral_inspection
false