Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Mar 31, 2020, 10:30 AM
  • 01 0452_01 0451_03312020_034125.mp4

Date
03/31/2020
W/O
818867
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00208
PipeID
P00934
Time
3:30 AM
Certificate
U-508-7069
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K7497
Sewer Name
01 HOLMES-WILLOWBROOK TRUNK
City
LOS ANGELES
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 01
Page No.
06
Purpose
Routine Assessment
Project
RFIR_WO_818867_TV01032_MAR2020
Sewer Type
Gravity
Material
NRCP
Shape
Circular
Height
15 in.
Width
15 in.
Upstream MH
01 0452
Downstream MH
01 0451
Dir. of Survey
Downstream
Length Surveyed
278.8 ft.
Total Length
278.8 ft.
Structural Index
0
Structural Quick
0000
Structural Rating
0
O&M Index
2
O&M Quick
2311
O&M Rating
7
Overall Index
2
Overall Quick
Overall Rating
7
Pipe schematic from manhole 01 0452 to 01 0451
MH: 01 0452MH: 01 0451downstream0 ft. MGO - General Observation - CONNECTION AT MH 3 O'CLOCK0 ft. MWL - Water Level, 5 %of cross sectional area0 ft. MWM - Water Mark, 25 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 01 04522.4 ft. MGO - General Observation - PIPE IS LINED58.8 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"74 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"102.1 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"104.3 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"119.4 ft. TFD - Tap Factory Made Defective, at 02 o'clock, -, within 8 inches of joint: NO, 6", 6" - POSSIBLE GREASE IN LATERAL127.4 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"145.1 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"153.3 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"178.2 ft. TFD - Tap Factory Made Defective, at 10 o'clock, -, within 8 inches of joint: NO, 6", 6" - POSSIBLE GREASE DEPOSITS IN LATERAL 50%203.6 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"206.2 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"242.6 ft. TFD - Tap Factory Made Defective, at 10 o'clock, -, within 8 inches of joint: NO, 6", 6" - ROOTS IN LATERAL242.6 ft. RFL - Roots Fine Lateral, at 10 o'clock260.7 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"278.8 ft. AMH - Downstream Manhole, Survey Ends - 01 0451

Observations (20)

DistanceCodeObservation
145.1TF
203.6TF
278.8AMH01 0451
0MGOCONNECTION AT MH 3 O'CLOCK
260.7TF
153.3TF
178.2TFDPOSSIBLE GREASE DEPOSITS IN LATERAL 50%
74TF
127.4TF
58.8TF
206.2TF
0MWL
242.6TFDROOTS IN LATERAL
102.1TF
0MWM
0AMH01 0452
104.3TF
119.4TFDPOSSIBLE GREASE IN LATERAL
242.6RFL
2.4MGOPIPE IS LINED

Properties (8)

additional_info
SC411104
custom_field_two
4
customer
LACSD
datetime
2020-03-31T03:30:44-07:00
documentation
PROPIPE
is_lateral_inspection
false
lining
CIPP
year_laid
37179