Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Apr 2, 2020, 10:34 AM
  • 01 0405_01 0404_04022020_034103.mp4

Date
04/02/2020
W/O
818867
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00208
PipeID
P00884
Time
3:34 AM
Certificate
U-508-7069
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K7510
Sewer Name
01 HOLMES-WILLOWBROOK TRUNK
City
LOS ANGELES
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 01
Page No.
13
Purpose
Routine Assessment
Project
RFIR_WO_818867_TV01032_MAR2020
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
18 in.
Width
18 in.
Upstream MH
01 0405
Downstream MH
01 0404
Dir. of Survey
Downstream
Length Surveyed
260.5 ft.
Total Length
260.5 ft.
Structural Index
0
Structural Quick
0000
Structural Rating
0
O&M Index
2
O&M Quick
2100
O&M Rating
2
Overall Index
2
Overall Quick
Overall Rating
2
Pipe schematic from manhole 01 0405 to 01 0404
MH: 01 0405MH: 01 0404downstream0 ft. MWM - Water Mark, 5 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 01 04050 ft. MWL - Water Level, 5 %of cross sectional area3.8 ft. MGO - General Observation - PIPE IS LINED27 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"113.1 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"130.7 ft. TFD - Tap Factory Made Defective, at 02 o'clock, -, within 8 inches of joint: NO, 6", 6" - BROKEN INSIDE CONNECTION173.9 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"260.5 ft. AMH - Downstream Manhole, Survey Ends - 01 0404260.5 ft. MGO - General Observation - CONNECTION AT MH 3 O'CLOCK

Observations (10)

DistanceCodeObservation
0MWM
0AMH01 0405
260.5AMH01 0404
27TF
130.7TFDBROKEN INSIDE CONNECTION
173.9TF
3.8MGOPIPE IS LINED
0MWL
113.1TF
260.5MGOCONNECTION AT MH 3 O'CLOCK

Properties (8)

additional_info
SC411108
custom_field_two
4
customer
LACSD
datetime
2020-04-02T03:34:03-07:00
documentation
PROPIPE
is_lateral_inspection
false
lining
CIPP
year_laid
35628