Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Apr 3, 2020, 10:18 AM
  • 01 0390_01 0389_04032020_033212.mp4

Date
04/03/2020
W/O
818867
Weather
Dry
Operator/Surveyor
N.ZAHREDDINE.
Sewer ID
Z00208
PipeID
P00869
Time
3:18 AM
Certificate
U-109-7948
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
K7319
Sewer Name
01 HOLMES-WILLOWBROOK TRUNK
City
LOS ANGELES
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 01
Page No.
16
Purpose
Routine Assessment
Project
RFIR_WO_818867_TV01032_MAR2020
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
18 in.
Width
18 in.
Upstream MH
01 0390
Downstream MH
01 0389
Dir. of Survey
Downstream
Length Surveyed
302.5 ft.
Total Length
302.6 ft.
Structural Index
0
Structural Quick
0000
Structural Rating
0
O&M Index
2
O&M Quick
2100
O&M Rating
2
Overall Index
2
Overall Quick
Overall Rating
2
Pipe schematic from manhole 01 0390 to 01 0389
MH: 01 0390MH: 01 0389downstream0 ft. AMH - Upstream Manhole, Survey Begins - 01 03900 ft. MWM - Water Mark, 25 %of cross sectional area0 ft. MWL - Water Level, 15 %of cross sectional area2 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start22.5 ft. TF - Tap Factory Made, at 01 o'clock, -, within 8 inches of joint: NO, 6"48.2 ft. TF - Tap Factory Made, at 01 o'clock, -, within 8 inches of joint: NO, 6"73.4 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"99.4 ft. TF - Tap Factory Made, at 01 o'clock, -, within 8 inches of joint: NO, 6"125 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"148.1 ft. TF - Tap Factory Made, at 01 o'clock, -, within 8 inches of joint: NO, 6"173.7 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"197 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"222.5 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"276.6 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"298.8 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish302.6 ft. MGO - General Observation - CONNECTION AT MH 3 O'CLOCK302.6 ft. AMH - Downstream Manhole, Survey Ends - 01 0389

Observations (17)

DistanceCodeObservation
0AMH01 0390
125TF
276.6TF
148.1TF
222.5TF
73.4TF
197TF
173.7TF
0MWM
0MWL
22.5TF
99.4TF
298.8DAGS
302.6MGOCONNECTION AT MH 3 O'CLOCK
302.6AMH01 0389
2DAGS
48.2TF

Properties (8)

additional_info
SC366947
custom_field_two
4
customer
LACSD
datetime
2020-04-03T03:18:28-07:00
documentation
PROPIPE
is_lateral_inspection
false
lining
CIPP
year_laid
35628