Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Apr 27, 2020, 11:59 AM
  • 08 1639_08 1638_4272020_045712.mp4

Date
04/27/2020
W/O
0823968
Weather
Dry
Operator/Surveyor
REVELES
Sewer ID
Z00539
PipeID
P06862
Time
4:59 AM
Certificate
U-115-06022630
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
H1406
Sewer Name
05 WEST TORRANCE TRUNK
City
TORRANCE
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 08
Page No.
13
Purpose
Routine Assessment
Project
20200427VMR_WEST_TORRANCE_TRUNK
Material
Vitrified Clay Pipe
Shape
Circular
Height
15 in.
Upstream MH
08 1639
Downstream MH
08 1638
Dir. of Survey
Downstream
Length Surveyed
120.8 ft.
Total Length
120.8 ft.
Structural Index
2
Structural Quick
3424
Structural Rating
25
O&M Index
2
O&M Quick
2200
O&M Rating
4
Overall Index
2
Overall Quick
Overall Rating
29
Pipe schematic from manhole 08 1639 to 08 1638
MH: 08 1639MH: 08 1638downstream0 ft. MWM - Water Mark, 40 %of cross sectional area0 ft. MWL - Water Level, 15 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 05:00 AM1.2 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 05 o'clock, , within 8 inches of joint: YES, Start1.2 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 07 to 09 o'clock, , within 8 inches of joint: YES, Start3.9 ft. CM - Crack Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES13.2 ft. CC - Crack Circumferential, from 12 to 01 o'clock, within 8 inches of joint: YES28.3 ft. CC - Crack Circumferential, from 10 to 12 o'clock, within 8 inches of joint: YES31 ft. CL - Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES31 ft. CL - Crack Longitudinal, at 10 o'clock, within 8 inches of joint: YES46.6 ft. CL - Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES46.6 ft. CC - Crack Circumferential, from 12 to 01 o'clock, within 8 inches of joint: YES49.5 ft. CC - Crack Circumferential, from 11 to 01 o'clock, within 8 inches of joint: YES67.8 ft. CL - Crack Longitudinal, at 10 o'clock, within 8 inches of joint: YES70.6 ft. CC - Crack Circumferential, from 09 to 11 o'clock, within 8 inches of joint: YES73.8 ft. CM - Crack Multiple, from 10 to 01 o'clock, within 8 inches of joint: YES107.4 ft. CM - Crack Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES111.2 ft. TF - Tap Factory Made, at 12 o'clock, -, within 8 inches of joint: YES, 4" - Open116.3 ft. CM - Crack Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES118.6 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 05 o'clock, , within 8 inches of joint: YES, Finish118.6 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 07 to 09 o'clock, , within 8 inches of joint: YES, Finish120.8 ft. TFA - Tap Factory Made Active, at 09 o'clock, -, within 8 inches of joint: NO, 4"

Observations (22)

DistanceCodeObservation
73.8CM
67.8CL
3.9CM
0MWM
0MWL
70.6CC
31CL
111.2TFOpen
107.4CM
13.2CC
49.5CC
46.6CL
28.3CC
1.2DAGS
116.3CM
120.8TFA
1.2DAGS
118.6DAGS
118.6DAGS
46.6CC
31CL
0AMH05:00 AM

Properties (5)

custom_field_two
2
customer
LACSD
datetime
2020-04-27T04:59:00-07:00
documentation
REVELES, OLIVER III, CASTILLO, SKINNER
is_lateral_inspection
false