Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Apr 21, 2020, 10:05 AM
  • 21 0395_21 0394_4212020_044640.mp4

Date
04/21/2020
W/O
0824053
Weather
Dry
Operator/Surveyor
REVELES
Sewer ID
Z00757
PipeID
P15601
Time
3:05 AM
Certificate
U-115-06022630
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
H1400
Sewer Name
21 CENTER STREET TRUNK
City
ROWLAND HEIGHTS
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 21
Page No.
35
Purpose
Maintenance Related
Project
20200421VMR_CENTER_STREET_TRUNK
Material
Vitrified Clay Pipe
Shape
Circular
Height
12 in.
Upstream MH
21 0395
Downstream MH
21 0394
Dir. of Survey
Downstream
Length Surveyed
353 ft.
Total Length
353 ft.
Structural Index
0
Structural Quick
0000
Structural Rating
0
O&M Index
2
O&M Quick
2200
O&M Rating
4
Overall Index
2
Overall Quick
Overall Rating
4
Pipe schematic from manhole 21 0395 to 21 0394
MH: 21 0395MH: 21 0394downstream0 ft. MWM - Water Mark, 20 %of cross sectional area0 ft. MWL - Water Level, 5 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 04:28 am7.8 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 07 to 08 o'clock, , within 8 inches of joint: YES, Start7.8 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 05 o'clock, , within 8 inches of joint: YES, Start351 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 07 to 08 o'clock, , within 8 inches of joint: YES, Finish351.1 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 05 o'clock, , within 8 inches of joint: YES, Finish353 ft. AMH - Downstream Manhole, Survey Ends - 04:42 am

Observations (8)

DistanceCodeObservation
353AMH04:42 am
351.1DAGS
7.8DAGS
0MWM
351DAGS
0MWL
0AMH04:28 am
7.8DAGS

Properties (4)

customer
LACSD
datetime
2020-04-21T03:05:21-07:00
documentation
REVELES, OLIVER III, CASTILLO, SKINNER
is_lateral_inspection
false