Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jan 28, 2020, 09:00 AM
  • 22 0288_22 0287_01282020_011226.mp4

Date
01/28/2020
W/O
808204
Weather
Dry
Operator/Surveyor
S. LOPEZ
Sewer ID
Z00793
PipeID
P16574
Time
1:00 AM
Certificate
U-111-11880
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K7288
Sewer Name
22 CAMERON TRUNK, SECTS 1,2,&3
City
WEST COVINA
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 22
Page No.
31
Purpose
Routine Assessment
Project
RFIR_WO_808204_TV22014_JAN2020
Sewer Type
Gravity
Material
NRCP
Shape
Circular
Height
12 in.
Width
12 in.
Upstream MH
22 0287
Downstream MH
22 0288
Dir. of Survey
Upstream
Length Surveyed
325.5 ft.
Total Length
325.5 ft.
Structural Index
3
Structural Quick
3L2L
Structural Rating
320
O&M Index
2
O&M Quick
2L00
O&M Rating
128
Overall Index
2
Overall Quick
Overall Rating
448
Pipe schematic from manhole 22 0287 to 22 0288
MH: 22 0287MH: 22 0288upstream0 ft. AMH - Upstream Manhole, Survey Ends - 22 02880 ft. MGO - General Observation - COCKROACHES IN MANHOLE2.1 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish2.1 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish2.1 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish35.7 ft. TFA - Tap Factory Made Active, at 02 o'clock, -, within 8 inches of joint: NO, 6"59.8 ft. TFA - Tap Factory Made Active, at 10 o'clock, -, within 8 inches of joint: NO, 6"124.5 ft. TFA - Tap Factory Made Active, at 02 o'clock, -, within 8 inches of joint: NO, 6"137.2 ft. TFA - Tap Factory Made Active, at 10 o'clock, -, within 8 inches of joint: NO, 6"190.3 ft. TFA - Tap Factory Made Active, at 02 o'clock, -, within 8 inches of joint: NO, 6"197.8 ft. TFA - Tap Factory Made Active, at 10 o'clock, -, within 8 inches of joint: NO, 6"239.1 ft. TFA - Tap Factory Made Active, at 02 o'clock, -, within 8 inches of joint: NO, 6"258.9 ft. TFA - Tap Factory Made Active, at 10 o'clock, -, within 8 inches of joint: NO, 6"312.3 ft. TFA - Tap Factory Made Active, at 10 o'clock, -, within 8 inches of joint: NO, 6"316.1 ft. TFA - Tap Factory Made Active, at 02 o'clock, -, within 8 inches of joint: NO, 6"323.5 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start323.5 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start323.5 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start325.5 ft. MWM - Water Mark, 20 %of cross sectional area325.5 ft. MWL - Water Level, 10 %of cross sectional area325.5 ft. AMH - Downstream Manhole, Survey Begins - 22 0287

Observation photos (1)

  • General Observation - COCKROACHES IN MANHOLE

    325.5 ft. - General Observation - COCKROACHES IN MANHOLE

Observations (21)

DistanceCodeObservation
201TFA
188.3TFA
2SSS
323.4SSS
0MWM
13.2TFA
0MWL
66.6TFA
325.5AMH22 0288
325.5MGOCOCKROACHES IN MANHOLE
265.7TFA
86.4TFA
135.2TFA
2DAGS
127.7TFA
323.4DAGS
323.4SAP
289.8TFA
2SAP
9.4TFA
0AMH22 0287

Properties (6)

additional_info
SC398774
custom_field_two
2
customer
LACSD
datetime
2020-01-28T01:00:53-08:00
documentation
PRO PIPE
is_lateral_inspection
false