Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Mar 23, 2020, 08:11 AM
  • B 0767_B 0766 _03232020_012650.mp4

Date
03/23/2020
W/O
813373
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00112
PipeID
P09234
Time
1:11 AM
Certificate
U-508-7069
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K7487
Sewer Name
B JOINT OUTFALL B - UNIT 8J
City
TEMPLE CITY
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 15
Page No.
16
Purpose
Routine Assessment
Project
RFIR_WO_813373_TV15062_FEB2020
Sewer Type
Gravity
Material
Reinforced Concrete Pipe
Shape
Circular
Height
36 in.
Width
36 in.
Upstream MH
B 0767
Downstream MH
B 0766
Dir. of Survey
Downstream
Length Surveyed
526.6 ft.
Total Length
526.6 ft.
Structural Index
3
Structural Quick
3T2T
Structural Rating
520
O&M Index
2
O&M Quick
2T00
O&M Rating
212
Overall Index
2
Overall Quick
Overall Rating
732
Pipe schematic from manhole B 0767 to B 0766
MH: B 0767MH: B 0766downstream0 ft. AMH - Upstream Manhole, Survey Begins - B 07670 ft. MWL - Water Level, 25 %of cross sectional area0 ft. MWM - Water Mark, 30 %of cross sectional area2 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start2 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start4 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start8.7 ft. MGO - General Observation - 70% MAG COAT33.1 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: YES, 4" - OPEN36 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"38.1 ft. TFD - Tap Factory Made Defective, at 10 o'clock, -, within 8 inches of joint: YES, 4", 6" - 60% GREASE-LATERAL/UNKNOWN129.6 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: YES, 4", 6"133.5 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: YES, 4", 6"213 ft. TFA - Tap Factory Made Active, at 02 o'clock, -, within 8 inches of joint: YES, 4", 6"217.6 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: YES, 4", 6"221.4 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: YES, 4", 6"288.8 ft. TFD - Tap Factory Made Defective, at 02 o'clock, -, within 8 inches of joint: YES, 4", 6" - 35% GREASE-LATERAL/UNKNOWN292.8 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: YES, 4", 6"392.9 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"396.9 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"488.2 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"492.8 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"504.6 ft. TB - Tap Break-In, at 07 o'clock, -, within 8 inches of joint: YES, 4", 6" - OPEN524 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish524 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish526.3 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish526.6 ft. AMH - Downstream Manhole, Survey Ends - B 0766

Observations (26)

DistanceCodeObservation
213TFA
392.9TFC
0AMHB 0767
526.6AMHB 0766
4SAV
524DAGS
38.1TFD60% GREASE-LATERAL/UNKNOWN
526.3SAV
33.1TFOPEN
504.6TBOPEN
129.6TFC
217.6TFC
36TF
0MWL
221.4TFC
488.2TFC
0MWM
292.8TFC
133.5TFC
524SSS
2DAGS
288.8TFD35% GREASE-LATERAL/UNKNOWN
396.9TFC
492.8TFC
2SSS
8.7MGO70% MAG COAT

Properties (6)

additional_info
SC398894
custom_field_two
3
customer
LACSD
datetime
2020-03-23T01:11:52-07:00
documentation
PROPIPE
is_lateral_inspection
false