Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Mar 23, 2020, 09:11 AM
  • B 0765_B 0764 _03232020_022647.mp4

Date
03/23/2020
W/O
813373
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00112
PipeID
P09232
Time
2:11 AM
Certificate
U-508-7069
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K7487
Sewer Name
B JOINT OUTFALL B - UNIT 8J
City
EL MONTE
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 15
Page No.
16
Purpose
Routine Assessment
Project
RFIR_WO_813373_TV15062_FEB2020
Sewer Type
Gravity
Material
Reinforced Concrete Pipe
Shape
Circular
Height
36 in.
Width
36 in.
Upstream MH
B 0765
Downstream MH
B 0764
Dir. of Survey
Downstream
Length Surveyed
586.6 ft.
Total Length
586.6 ft.
Structural Index
3
Structural Quick
3V2V
Structural Rating
583
O&M Index
2
O&M Quick
2V11
O&M Rating
235
Overall Index
2
Overall Quick
Overall Rating
818
Pipe schematic from manhole B 0765 to B 0764
MH: B 0765MH: B 0764downstream0 ft. MWM - Water Mark, 25 %of cross sectional area0 ft. MWL - Water Level, 20 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - B 07652 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start2 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start3.9 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start3.9 ft. MGO - General Observation - 75% MAG COAT115.3 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"170 ft. TFD - Tap Factory Made Defective, at 02 o'clock, -, within 8 inches of joint: YES, 4", 6" - 40% GREASE-LATERAL/OPEN173.8 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"258.2 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"262.3 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"362.1 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"366 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"458.1 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"462 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"558.1 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"584 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish584 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish586 ft. VC - Vermin Cockroach, within 8 inches of joint: NO - @ MH586.6 ft. AMH - Downstream Manhole, Survey Ends - B 0764586.6 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish

Observation photos (1)

  • Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    3.9 ft. - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

Observations (22)

DistanceCodeObservation
258.2TFC
362.1TFC
462TFC
262.3TFC
586VC@ MH
115.3TFC
458.1TFC
0MWM
584DAGS
170TFD40% GREASE-LATERAL/OPEN
366TFC
2DAGS
3.9SAV
584SSS
0MWL
3.9MGO75% MAG COAT
2SSS
586.6AMHB 0764
586.6SAV
173.8TFC
0AMHB 0765
558.1TFC

Properties (6)

additional_info
SC398894
custom_field_two
3
customer
LACSD
datetime
2020-03-23T02:11:45-07:00
documentation
PROPIPE
is_lateral_inspection
false