Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Apr 16, 2020, 08:28 AM
  • 16 0025_16 0024_4162020_015314.mp4

Date
04/16/2020
W/O
023979
Weather
Dry
Operator/Surveyor
REVELES
Sewer ID
Z00668
PipeID
P13749
Time
1:28 AM
Certificate
U-115-6022630
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
H1395
Sewer Name
17 DISTRICT #17 MAIN TRUNK
City
PASADENA
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 17
Page No.
06
Purpose
Maintenance Related
Project
20200416MVR_DISTRICT_17_MAIN_TRUNK
Material
Vitrified Clay Pipe
Shape
Circular
Height
15 in.
Upstream MH
16 0025
Downstream MH
16 0024
Dir. of Survey
Downstream
Length Surveyed
396.3 ft.
Total Length
396.3 ft.
Structural Index
0
Structural Quick
0000
Structural Rating
0
O&M Index
3
O&M Quick
4111
O&M Rating
5
Overall Index
3
Overall Quick
Overall Rating
5
Pipe schematic from manhole 16 0025 to 16 0024
MH: 16 0025MH: 16 0024downstream0 ft. MWL - Water Level, 15 %of cross sectional area0 ft. MWM - Water Mark, 30 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 01:50 AM244.7 ft. RBC - Roots Ball Connection, from 12 to 07 o'clock, 55 %, within 8 inches of joint: NO347.4 ft. RFC - Roots Fine Connection, from 08 to 10 o'clock, within 8 inches of joint: YES396.3 ft. AMH - Downstream Manhole, Survey Ends - 02:07 AM

Observation photos (1)

  • Roots Ball Connection, from 12 to 07 o'clock, 55 %, within 8 inches of joint: NO

    244.7 ft. - Roots Ball Connection, from 12 to 07 o'clock, 55 %, within 8 inches of joint: NO

Observations (6)

DistanceCodeObservation
0MWL
347.4RFC
244.7RBC
0MWM
396.3AMH02:07 AM
0AMH01:50 AM

Properties (4)

customer
LACSD
datetime
2020-04-16T01:28:51-07:00
documentation
REVELES, OLIVER III, CASTILLO., SKINNER
is_lateral_inspection
false