Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Mar 16, 2020, 08:25 AM
  • B 0780_B 0779 _03162020_012903.mp4

Date
03/16/2020
W/O
813373
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00112
PipeID
P09247
Time
1:25 AM
Certificate
U-508-7069
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K7485
Sewer Name
B JOINT OUTFALL B - UNIT 8J
City
TEMPLE CITY
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 15
Page No.
11
Purpose
Routine Assessment
Project
RFIR_WO_813373_TV15062_FEB2020
Sewer Type
Gravity
Material
Reinforced Concrete Pipe
Shape
Circular
Height
42 in.
Width
42 in.
Upstream MH
B 0780
Downstream MH
B 0779
Dir. of Survey
Downstream
Length Surveyed
42.2 ft.
Total Length
42.2 ft.
Structural Index
3
Structural Quick
3828
Structural Rating
40
O&M Index
2
O&M Quick
2800
O&M Rating
16
Overall Index
2
Overall Quick
Overall Rating
56
Pipe schematic from manhole B 0780 to B 0779
MH: B 0780MH: B 0779downstream0 ft. MWM - Water Mark, 30 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - B 07800 ft. MWL - Water Level, 25 %of cross sectional area2 ft. MGO - General Observation - 70% MAG COAT2 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start2 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start2.1 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start40 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish40 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish41.2 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish42.2 ft. AMH - Downstream Manhole, Survey Ends - B 0779

Observation photos (1)

  • Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    2.1 ft. - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

Observations (11)

DistanceCodeObservation
0MWM
40DAGS
2MGO70% MAG COAT
41.2SAV
0AMHB 0780
2.1SAV
0MWL
2SSS
42.2AMHB 0779
2DAGS
40SSS

Properties (6)

additional_info
SC398892
custom_field_two
3
customer
LACSD
datetime
2020-03-16T01:25:06-07:00
documentation
PROPIPE
is_lateral_inspection
false