Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Mar 20, 2020, 06:50 AM
  • B 0773_B 0772 _03202020_000430.mp4

Date
03/19/2020
W/O
813373
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00112
PipeID
P09240
Time
11:50 PM
Certificate
U-508-7069
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K7486
Sewer Name
B JOINT OUTFALL B - UNIT 8J
City
TEMPLE CITY
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 15
Page No.
16
Purpose
Routine Assessment
Project
RFIR_WO_813373_TV15062_FEB2020
Sewer Type
Gravity
Material
Reinforced Concrete Pipe
Shape
Circular
Height
36 in.
Width
36 in.
Upstream MH
B 0773
Downstream MH
B 0772
Dir. of Survey
Downstream
Length Surveyed
552.9 ft.
Total Length
552.9 ft.
Structural Index
3
Structural Quick
5U3j
Structural Rating
1418
O&M Index
2
O&M Quick
2U11
O&M Rating
221
Overall Index
3
Overall Quick
Overall Rating
1639
Pipe schematic from manhole B 0773 to B 0772
MH: B 0773MH: B 0772downstream0 ft. MWM - Water Mark, 30 %of cross sectional area0 ft. MWL - Water Level, 25 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - B 07732 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start2 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start2 ft. SRV - Surface Reinforcement Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start2.1 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start2.1 ft. MGO - General Observation - 75% MAG COAT23.6 ft. SAP - Surface Aggregate Projecting, from 10 to 02 o'clock, within 8 inches of joint: YES, Start550 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish550 ft. SRV - Surface Reinforcement Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish550 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish552 ft. VC - Vermin Cockroach, within 8 inches of joint: NO - @ MH552.9 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish552.9 ft. SAP - Surface Aggregate Projecting, from 10 to 02 o'clock, within 8 inches of joint: YES, Finish552.9 ft. AMH - Downstream Manhole, Survey Ends - B 0772552.9 ft. MGO - General Observation - CONN @ MH 9 O'CLOCK/OPEN

Observation photos (2)

  • Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    2.1 ft. - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Surface Aggregate Projecting, from 10 to 02 o'clock, within 8 inches of joint: YES, Start

    23.6 ft. - Surface Aggregate Projecting, from 10 to 02 o'clock, within 8 inches of joint: YES, Start

Observations (17)

DistanceCodeObservation
550SSS
2.1SAV
0MWM
552.9SAV
2SSS
552.9SAP
0MWL
550SRV
2DAGS
0AMHB 0773
550DAGS
552VC@ MH
23.6SAP
552.9AMHB 0772
2.1MGO75% MAG COAT
2SRV
552.9MGOCONN @ MH 9 O'CLOCK/OPEN

Properties (5)

custom_field_two
3
customer
LACSD
datetime
2020-03-19T23:50:19-07:00
documentation
PROPIPE
is_lateral_inspection
false