Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Mar 11, 2020, 06:11 AM
  • B 0789_B 0787 _03102020_234714.mp4

Date
03/10/2020
W/O
813373
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00112
PipeID
P09256
Time
11:11 PM
Certificate
U-508-7069
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K7484
Sewer Name
B JOINT OUTFALL B - UNIT 8J
City
ARCADIA
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 15
Page No.
11
Purpose
Routine Assessment
Project
RFIR_WO_813373_TV15062_FEB2020
Sewer Type
Gravity
Material
Reinforced Concrete Pipe
Shape
Circular
Height
42 in.
Width
42 in.
Upstream MH
B 0789
Downstream MH
B 0787
Dir. of Survey
Downstream
Length Surveyed
564.7 ft.
Total Length
564.7 ft.
Structural Index
4
Structural Quick
5U3U
Structural Rating
896
O&M Index
2
O&M Quick
2U00
O&M Rating
224
Overall Index
3
Overall Quick
Overall Rating
1120
Pipe schematic from manhole B 0789 to B 0787
MH: B 0789MH: B 0787downstream0 ft. MWL - Water Level, 30 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - B 07890 ft. MWM - Water Mark, 35 %of cross sectional area2 ft. SRV - Surface Reinforcement Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start2 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start3.7 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start4 ft. MGO - General Observation - 80% MAG COAT562 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish562 ft. SRV - Surface Reinforcement Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish562.8 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish563.6 ft. MGO - General Observation - CONN @ MH 3 O'CLOCK/ACTIVE564.7 ft. AMH - Downstream Manhole, Survey Ends - B 0787

Observation photos (1)

  • Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    3.7 ft. - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

Observations (12)

DistanceCodeObservation
563.6MGOCONN @ MH 3 O'CLOCK/ACTIVE
0MWL
0AMHB 0789
562DAGS
564.7AMHB 0787
4MGO80% MAG COAT
562SRV
2SRV
562.8SAV
0MWM
3.7SAV
2DAGS

Properties (6)

additional_info
SC398891
custom_field_two
3
customer
LACSD
datetime
2020-03-10T23:11:45-07:00
documentation
PROPIPE
is_lateral_inspection
false