Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Mar 5, 2020, 11:06 AM
  • A 0215_A 0214 _03052020_042101.mp4

Date
03/05/2020
W/O
813493
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00323
PipeID
P08151
Time
3:06 AM
Certificate
U-508-7069
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K7479
Sewer Name
A JOA-1A LOS COYOTES WRP INTERCEPTOR
City
SOUTH GATE
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 02
Page No.
26
Purpose
Routine Assessment
Project
RFIR_WO_813493_TV02346_FEB2020
Sewer Type
Gravity
Material
Reinforced Concrete Pipe
Shape
Circular
Height
75 in.
Width
75 in.
Upstream MH
A 0215
Downstream MH
A 0214
Dir. of Survey
Downstream
Length Surveyed
12.5 ft.
Total Length
12.5 ft.
Structural Index
4
Structural Quick
5131
Structural Rating
8
O&M Index
4
O&M Quick
4100
O&M Rating
4
Overall Index
4
Overall Quick
Overall Rating
12
Pipe schematic from manhole A 0215 to A 0214
MH: A 0215MH: A 0214downstream0 ft. AMH - Upstream Manhole, Survey Begins - A 02150 ft. MWM - Water Mark, 25 %of cross sectional area0 ft. MWL - Water Level, 20 %of cross sectional area3.2 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start3.4 ft. DAR - Deposits Attached Ragging, 25 %of cross sectional area, from 06 to 07 o'clock, , within 8 inches of joint: YES3.4 ft. SRV - Surface Reinforcement Visible, from 10 to 02 o'clock, within 8 inches of joint: YES, Start12.5 ft. SRV - Surface Reinforcement Visible, from 10 to 02 o'clock, within 8 inches of joint: YES, Finish12.5 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish12.5 ft. MSA - Survey Abandoned - HEAVY DEBRIS IN PIPE

Observation photos (4)

  • Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    3.2 ft. - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Deposits Attached Ragging, 25 %of cross sectional area, from 06 to 07 o'clock,  , within 8 inches of joint: YES

    3.4 ft. - Deposits Attached Ragging, 25 %of cross sectional area, from 06 to 07 o'clock, , within 8 inches of joint: YES

  • Surface Reinforcement Visible, from 10 to 02 o'clock, within 8 inches of joint: YES, Start

    3.4 ft. - Surface Reinforcement Visible, from 10 to 02 o'clock, within 8 inches of joint: YES, Start

  • Survey Abandoned - HEAVY DEBRIS IN PIPE

    12.5 ft. - Survey Abandoned - HEAVY DEBRIS IN PIPE

Observations (9)

DistanceCodeObservation
3.4DAR
12.5SRV
12.5SAP
3.2SAP
12.5MSAHEAVY DEBRIS IN PIPE
3.4SRV
0AMHA 0215
0MWM
0MWL

Properties (7)

additional_info
SC398886
custom_field_two
2
customer
LACSD
datetime
2020-03-05T03:06:13-08:00
documentation
PROPIPE
is_lateral_inspection
false
year_laid
28636