Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Mar 5, 2020, 07:16 AM
  • A 0159_A 0158 _03052020_004536.mp4

Date
03/04/2020
W/O
813493
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00323
PipeID
P08096
Time
11:16 PM
Certificate
U-508-7069
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K7479
Sewer Name
A JOA-1A LOS COYOTES WRP INTERCEPTOR
City
BELLFLOWER
Loc. details
Main Highway - Urban
Location Code
A
Use of Sewer
Sanitary Sewer
District
District 02
Page No.
37
Purpose
Routine Assessment
Project
RFIR_WO_813493_TV02346_FEB2020
Sewer Type
Gravity
Material
Reinforced Concrete Pipe
Shape
Circular
Height
78 in.
Width
78 in.
Upstream MH
A 0159
Downstream MH
A 0158
Dir. of Survey
Downstream
Length Surveyed
851.3 ft.
Total Length
851.4 ft.
Structural Index
4
Structural Quick
5131
Structural Rating
8
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
4
Overall Quick
Overall Rating
8
Pipe schematic from manhole A 0159 to A 0158
MH: A 0159MH: A 0158downstream0 ft. MWM - Water Mark, 25 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - A 01590 ft. MWL - Water Level, 15 %of cross sectional area2.9 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start3.3 ft. SRV - Surface Reinforcement Visible, from 09 to 03 o'clock, within 8 inches of joint: YES, Start49.7 ft. SRV - Surface Reinforcement Visible, from 09 to 03 o'clock, within 8 inches of joint: YES, Finish851.3 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish851.4 ft. AMH - Downstream Manhole, Survey Ends - A 0158

Observation photos (2)

  • Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    2.9 ft. - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Surface Reinforcement Visible, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

    3.3 ft. - Surface Reinforcement Visible, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

Observations (8)

DistanceCodeObservation
0MWM
3.3SRV
0AMHA 0159
2.9SAP
49.7SRV
851.4AMHA 0158
0MWL
851.3SAP

Properties (7)

additional_info
SC398886
custom_field_two
2
customer
LACSD
datetime
2020-03-04T23:16:00-08:00
documentation
PROPIPE
is_lateral_inspection
false
year_laid
28048