Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Mar 19, 2020, 09:55 AM
  • 14 0536_14 0535B _03192020_030306.mp4

Date
03/19/2020
W/O
813897
Weather
Dry
Operator/Surveyor
S. LOPEZ
Sewer ID
Z00588
PipeID
P18627
Time
2:55 AM
Certificate
U-111-11880
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K7445
Sewer Name
14 35TH STREET WEST TRUNK
City
LANCASTER
Loc. details
Easement/Right of Way
Location Code
D
Use of Sewer
Sanitary Sewer
District
District 14
Page No.
26
Purpose
Routine Assessment
Project
RFIR_WO_813897_TV14042_FEB2020
Sewer Type
Gravity
Material
Reinforced Concrete Pipe
Shape
Rectangular
Height
27 in.
Width
27 in.
Upstream MH
14 0536
Downstream MH
14 0535B
Dir. of Survey
Downstream
Length Surveyed
193.6 ft.
Total Length
193.6 ft.
Structural Index
2
Structural Quick
3F2G
Structural Rating
187
O&M Index
2
O&M Quick
2G00
O&M Rating
76
Overall Index
2
Overall Quick
Overall Rating
263
Pipe schematic from manhole 14 0536 to 14 0535B
MH: 14 0536MH: 14 0535Bdownstream0 ft. MWL - Water Level, 20 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 14 05360 ft. MWM - Water Mark, 25 %of cross sectional area2 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start2 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start2 ft. SZ - Surface Other, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - 70% MAG COAT5.7 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start190.9 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish190.9 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish190.9 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish193 ft. MGO - General Observation - CONN @ MH 3 O'CLOCK/ACTIVE193 ft. MGO - General Observation - CONN @ MH 9 O'CLCOK/ACTIVE193 ft. SZ - Surface Other, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish - 70% MAG COAT193.6 ft. AMH - Downstream Manhole, Survey Ends - 14 0535B

Observation photos (3)

  • Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    2 ft. - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock,  , within 8 inches of joint: YES, Start

    2 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start

  • Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    5.7 ft. - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

Observations (14)

DistanceCodeObservation
190.9SAP
190.9SSS
5.7SAP
193.6AMH14 0535B
193MGOCONN @ MH 3 O'CLOCK/ACTIVE
2SSS
0MWL
0AMH14 0536
0MWM
190.9DAGS
2DAGS
2SZ70% MAG COAT
193MGOCONN @ MH 9 O'CLCOK/ACTIVE
193SZ70% MAG COAT

Properties (6)

additional_info
SC398835
custom_field_two
2
customer
LACSD
datetime
2020-03-19T02:55:21-07:00
documentation
PRO PIPE
is_lateral_inspection
false