Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Mar 17, 2020, 07:02 AM
  • 14 0553_14 0552 _03172020_002042.mp4

Date
03/17/2020
W/O
813897
Weather
Light Rain
Operator/Surveyor
S. LOPEZ
Sewer ID
Z00588
PipeID
P18647
Time
12:02 AM
Certificate
U-111-11880
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K7442
Sewer Name
14 35TH STREET WEST TRUNK
City
LANCASTER
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 14
Page No.
30
Purpose
Routine Assessment
Project
RFIR_WO_813897_TV14042_FEB2020
Sewer Type
Gravity
Material
Reinforced Concrete Pipe
Shape
Circular
Height
24 in.
Width
24 in.
Upstream MH
14 0552
Downstream MH
14 0553
Dir. of Survey
Upstream
Length Surveyed
480.5 ft.
Total Length
480.5 ft.
Structural Index
3
Structural Quick
5R3R
Structural Rating
950
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
3
Overall Quick
Overall Rating
950
Pipe schematic from manhole 14 0552 to 14 0553
MH: 14 0552MH: 14 0553upstream0 ft. AMH - Upstream Manhole, Survey Ends - 14 05531.4 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish1.4 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish2.5 ft. SRV - Surface Reinforcement Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish478.5 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start478.5 ft. MGO - General Observation - 70% MAG COATING THROUGHOUT478.5 ft. SRV - Surface Reinforcement Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start478.5 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start480.5 ft. MWM - Water Mark, 35 %of cross sectional area480.5 ft. MWL - Water Level, 30 %of cross sectional area480.5 ft. AMH - Downstream Manhole, Survey Begins - 14 0552

Observation photos (3)

  • Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    2 ft. - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • General Observation - 70% MAG COATING THROUGHOUT

    2 ft. - General Observation - 70% MAG COATING THROUGHOUT

  • Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    2 ft. - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

Observations (11)

DistanceCodeObservation
479.1SAP
0MWM
2SAP
0MWL
2MGO70% MAG COATING THROUGHOUT
2SRV
2SSS
0AMH14 0552
478SRV
479.1SSS
480.5AMH14 0553

Properties (6)

additional_info
SC398832
custom_field_two
3
customer
LACSD
datetime
2020-03-17T00:02:14-07:00
documentation
PRO PIPE
is_lateral_inspection
false