Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Mar 19, 2020, 06:30 AM
  • 14 0548A_14 0548 _03182020_234330.mp4

Date
03/18/2020
W/O
813897
Weather
Dry
Operator/Surveyor
S. LOPEZ
Sewer ID
Z00588
PipeID
P18641
Time
11:30 PM
Certificate
U-111-11880
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K7445
Sewer Name
14 35TH STREET WEST TRUNK
City
LANCASTER
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 14
Page No.
26
Purpose
Routine Assessment
Project
RFIR_WO_813897_TV14042_FEB2020
Sewer Type
Gravity
Material
Reinforced Concrete Pipe
Shape
Circular
Height
24 in.
Width
24 in.
Upstream MH
14 0548A
Downstream MH
14 0548
Dir. of Survey
Downstream
Length Surveyed
467.5 ft.
Total Length
467.5 ft.
Structural Index
3
Structural Quick
3R2R
Structural Rating
465
O&M Index
2
O&M Quick
2R00
O&M Rating
186
Overall Index
2
Overall Quick
Overall Rating
651
Pipe schematic from manhole 14 0548A to 14 0548
MH: 14 0548AMH: 14 0548downstream0 ft. MWL - Water Level, 20 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 14 0548A0 ft. MWM - Water Mark, 25 %of cross sectional area0.1 ft. MGO - General Observation - CONN @ MH 9 O'CLOCK/ACTIVE0.1 ft. MGO - General Observation - CONN @ MH 3 O' CLOCK/ACTIVE2 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start2 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start2 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start2 ft. SZ - Surface Other, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - 65% MAG COAT465 ft. SZ - Surface Other, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish - 65% MAG COAT465.9 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish465.9 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish465.9 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish467.5 ft. AMH - Downstream Manhole, Survey Ends - 14 0548467.5 ft. MGO - General Observation - CONN @ MH 3 O'CLOCK/ACTIVE

Observation photos (3)

  • Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    2 ft. - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    2 ft. - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock,  , within 8 inches of joint: YES, Start

    2 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start

Observations (15)

DistanceCodeObservation
465.9DAGS
2SAP
467.5AMH14 0548
467.5MGOCONN @ MH 3 O'CLOCK/ACTIVE
0.1MGOCONN @ MH 9 O'CLOCK/ACTIVE
0.1MGOCONN @ MH 3 O' CLOCK/ACTIVE
465.9SAP
465SZ65% MAG COAT
2SSS
0MWL
0AMH14 0548A
0MWM
465.9SSS
2DAGS
2SZ65% MAG COAT

Properties (6)

additional_info
SC398835
custom_field_two
2
customer
LACSD
datetime
2020-03-18T23:30:55-07:00
documentation
PRO PIPE
is_lateral_inspection
false