- Date
- 03/18/2020
- W/O
- 813897
- Weather
- Dry
- Operator/Surveyor
- S. LOPEZ
- Sewer ID
- Z00588
- PipeID
- P18640
- Time
- 11:43 PM
- Certificate
- U-111-11880
- System Owner
- LACSD
- Date Cleaned
- —
- Pre-Cleaning
- No Pre-Cleaning
- Media Label
- K7445
- Sewer Name
- 14 35TH STREET WEST TRUNK
- City
- LANCASTER
- Loc. details
- Light Highway
- Location Code
- C
- Use of Sewer
- Sanitary Sewer
- District
- District 14
- Page No.
- 26
- Purpose
- Routine Assessment
- Project
- RFIR_WO_813897_TV14042_FEB2020
- Sewer Type
- Gravity
- Material
- Reinforced Concrete Pipe
- Shape
- Circular
- Height
- 27 in.
- Width
- 27 in.
- Upstream MH
- 14 0548
- Downstream MH
- 14 0547
- Dir. of Survey
- Downstream
- Length Surveyed
- 321.6 ft.
- Total Length
- 321.6 ft.
- Structural Index
- 3
- Structural Quick
- 5L3L
- Structural Rating
- 630
- O&M Index
- 2
- O&M Quick
- 2L00
- O&M Rating
- 126
- Overall Index
- 3
- Overall Quick
- —
- Overall Rating
- 756
Pipe schematic from manhole 14 0548 to 14 0547 Observation photos (3)

2 ft. - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

2 ft. - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

2 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start