Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Mar 2, 2020, 10:52 AM
  • J 0178_J 0177 _03022020_041305.mp4

Date
03/02/2020
W/O
813476
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00055
PipeID
P11417
Time
2:52 AM
Certificate
U-508-7069
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K7473
Sewer Name
J JOINT OUTFALL J - UNIT 1C
City
SAN PEDRO
Loc. details
Main Highway - Urban
Location Code
A
Use of Sewer
Sanitary Sewer
District
District 05
Page No.
47A
Purpose
Routine Assessment
Project
RFIR_WO_813476_TV05341_FEB2020
Sewer Type
Gravity
Material
Reinforced Concrete Pipe
Shape
Circular
Height
21 in.
Width
21 in.
Upstream MH
J 0178
Downstream MH
J 0177
Dir. of Survey
Downstream
Length Surveyed
530.2 ft.
Total Length
530.2 ft.
Structural Index
3
Structural Quick
3200
Structural Rating
6
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
3
Overall Quick
Overall Rating
6
Pipe schematic from manhole J 0178 to J 0177
MH: J 0178MH: J 0177downstream0 ft. MWL - Water Level, 10 %of cross sectional area0 ft. MWM - Water Mark, 20 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - J 01783.1 ft. MGO - General Observation - MAG COAT3.1 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start66.3 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start66.3 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish530.2 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish530.2 ft. AMH - Downstream Manhole, Survey Ends - J 0177

Observation photos (2)

  • Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    3.1 ft. - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    66.3 ft. - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

Observations (9)

DistanceCodeObservation
0MWL
66.3SAP
0MWM
3.1MGOMAG COAT
66.3SAV
530.2SAP
0AMHJ 0178
3.1SAV
530.2AMHJ 0177

Properties (7)

additional_info
SC398879
custom_field_three
AGGREGATE PROJECTING
custom_field_two
2
customer
LACSD
datetime
2020-03-02T02:52:36-08:00
documentation
PROPIPE
is_lateral_inspection
false