Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Mar 3, 2020, 08:24 AM
  • 15 0762_15 0761 _03032020_014227.mp4

Date
03/03/2020
W/O
813447
Weather
Dry
Operator/Surveyor
M.MARTINEZ
Sewer ID
Z00593
PipeID
P12963
Time
12:24 AM
Certificate
U-115-06022794
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
K7363
Sewer Name
15 ARCADIA-SIERRA MADRE TRUNK, SECTS 2&5
City
ARCADIA
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 15
Page No.
08
Purpose
Routine Assessment
Project
RFIR_WO_813447_TV15146_FEB2020
Sewer Type
Gravity
Material
NRCP
Shape
Circular
Height
15 in.
Width
15 in.
Upstream MH
15 0762
Downstream MH
15 0761
Dir. of Survey
Downstream
Length Surveyed
205.4 ft.
Total Length
205.5 ft.
Structural Index
3
Structural Quick
3G2G
Structural Rating
200
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
3
Overall Quick
Overall Rating
200
Pipe schematic from manhole 15 0762 to 15 0761
MH: 15 0762MH: 15 0761downstream0 ft. AMH - Upstream Manhole, Survey Begins - 15 07620 ft. MWM - Water Mark, 40 %of cross sectional area0 ft. MWL - Water Level, 20 %of cross sectional area0 ft. MGO - General Observation - CONNECTION AT MH 3 O'CLOCK2 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start2 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start16.4 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: YES, 8"61.8 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: YES, 8"98.9 ft. TB - Tap Break-In, at 03 o'clock, -, within 8 inches of joint: YES, 8"127.7 ft. TB - Tap Break-In, at 11 o'clock, -, within 8 inches of joint: YES, 8"203.6 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish203.6 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish205 ft. MGO - General Observation - CONNECTION AT MH 9 O'CLOCK205.5 ft. AMH - Downstream Manhole, Survey Ends - 15 0761

Observation photos (2)

  • Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    2 ft. - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    2 ft. - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

Observations (14)

DistanceCodeObservation
98.9TB
203.6SSS
0AMH15 0762
2SSS
0MWM
2SAV
0MWL
203.6SAV
205.5AMH15 0761
0MGOCONNECTION AT MH 3 O'CLOCK
127.7TB
205MGOCONNECTION AT MH 9 O'CLOCK
16.4TF
61.8TF

Properties (5)

custom_field_two
3
customer
LACSD
datetime
2020-03-03T00:24:28-08:00
documentation
PRO PIPE
is_lateral_inspection
false