Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Mar 3, 2020, 10:41 AM
  • 15 0755_15 0754 _03032020_035614.mp4

Date
03/03/2020
W/O
813447
Weather
Dry
Operator/Surveyor
M.MARTINEZ
Sewer ID
Z00593
PipeID
P12955
Time
2:41 AM
Certificate
U-115-06022794
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
K7363
Sewer Name
15 ARCADIA-SIERRA MADRE TRUNK, SECTS 2&5
City
ARCADIA
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 15
Page No.
08
Purpose
Routine Assessment
Project
RFIR_WO_813447_TV15146_FEB2020
Sewer Type
Gravity
Material
NRCP
Shape
Circular
Height
15 in.
Width
15 in.
Upstream MH
15 0755
Downstream MH
15 0754
Dir. of Survey
Downstream
Length Surveyed
95.7 ft.
Total Length
95.7 ft.
Structural Index
3
Structural Quick
3C2C
Structural Rating
90
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
3
Overall Quick
Overall Rating
90
Pipe schematic from manhole 15 0755 to 15 0754
MH: 15 0755MH: 15 0754downstream0 ft. AMH - Upstream Manhole, Survey Begins - 15 07550 ft. MWM - Water Mark, 40 %of cross sectional area0 ft. MWL - Water Level, 10 %of cross sectional area2 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start3.1 ft. SSS - Surface Spalling, from 09 to 03 o'clock, within 8 inches of joint: YES, Start35.9 ft. TB - Tap Break-In, at 02 o'clock, -, within 8 inches of joint: YES, 8"54 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: YES, 8"93.3 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish93.3 ft. SSS - Surface Spalling, from 09 to 03 o'clock, within 8 inches of joint: YES, Finish95.7 ft. MGO - General Observation - CONNECTION AT MH 9 O'CLOCK95.7 ft. AMH - Downstream Manhole, Survey Ends - 15 0754

Observation photos (2)

  • Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    2 ft. - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Surface Spalling, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

    3.1 ft. - Surface Spalling, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

Observations (11)

DistanceCodeObservation
93.3SAV
54TF
0AMH15 0755
35.9TB
3.1SSS
95.7MGOCONNECTION AT MH 9 O'CLOCK
95.7AMH15 0754
0MWM
0MWL
2SAV
93.3SSS

Properties (5)

custom_field_two
3
customer
LACSD
datetime
2020-03-03T02:41:35-08:00
documentation
PRO PIPE
is_lateral_inspection
false