Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Feb 26, 2020, 09:20 AM
  • J 0277_J 0276_02262020_023808.mp4

Date
02/26/2020
W/O
813409
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00059
PipeID
P11517
Time
1:20 AM
Certificate
U-508-7069
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K7466
Sewer Name
J JOINT OUTFALL J - UNIT 1G
City
RANCHO PALOS VERDES
Loc. details
Main Highway - Urban
Location Code
A
Use of Sewer
Sanitary Sewer
District
District 05
Page No.
45
Purpose
Routine Assessment
Project
RFIR_WO_813409_TV05169_FEB2020
Sewer Type
Gravity
Material
Reinforced Concrete Pipe
Shape
Circular
Height
24 in.
Width
24 in.
Upstream MH
J 0277
Downstream MH
J 0276
Dir. of Survey
Downstream
Length Surveyed
254.7 ft.
Total Length
254.7 ft.
Structural Index
3
Structural Quick
3100
Structural Rating
3
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
3
Overall Quick
Overall Rating
3
Pipe schematic from manhole J 0277 to J 0276
MH: J 0277MH: J 0276downstream0 ft. MWM - Water Mark, 20 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - J 02770 ft. MWL - Water Level, 5 %of cross sectional area4.3 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start4.3 ft. MGO - General Observation - MAG COAT254.7 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish254.7 ft. AMH - Downstream Manhole, Survey Ends - J 0276254.7 ft. MGO - General Observation - CONNECTION AT MH 9 O'CLOCK

Observation photos (1)

  • Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    4.3 ft. - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

Observations (8)

DistanceCodeObservation
254.7SAV
254.7AMHJ 0276
4.3SAV
4.3MGOMAG COAT
0MWM
254.7MGOCONNECTION AT MH 9 O'CLOCK
0AMHJ 0277
0MWL

Properties (6)

additional_info
SC398871
custom_field_two
3
customer
LACSD
datetime
2020-02-26T01:20:43-08:00
documentation
PROPIPE
is_lateral_inspection
false