Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Feb 25, 2020, 08:13 AM
  • J 0305A_J 0305_02252020_011654.mp4

Date
02/25/2020
W/O
813409
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00059
PipeID
P11547
Time
12:13 AM
Certificate
U-508-7069
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K7465
Sewer Name
J JOINT OUTFALL J - UNIT 1G
City
RANCHO PALOS VERDES
Loc. details
Main Highway - Urban
Location Code
A
Use of Sewer
Sanitary Sewer
District
District 05
Page No.
41
Purpose
Routine Assessment
Project
RFIR_WO_813409_TV05169_FEB2020
Sewer Type
Gravity
Material
Reinforced Concrete Pipe
Shape
Circular
Height
21 in.
Width
21 in.
Upstream MH
J 0305A
Downstream MH
J 0305
Dir. of Survey
Downstream
Length Surveyed
98.3 ft.
Total Length
98.3 ft.
Structural Index
3
Structural Quick
3100
Structural Rating
3
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
3
Overall Quick
Overall Rating
3
Pipe schematic from manhole J 0305A to J 0305
MH: J 0305AMH: J 0305downstream0 ft. MWL - Water Level, 10 %of cross sectional area0 ft. MWM - Water Mark, 25 %of cross sectional area0 ft. MGO - General Observation - CONNECTION AT MH 9 O'CLOCK0 ft. AMH - Upstream Manhole, Survey Begins - J 0305A4.6 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start4.6 ft. MGO - General Observation - MAG COAT98.3 ft. AMH - Downstream Manhole, Survey Ends - J 030598.3 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish

Observation photos (1)

  • Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    4.6 ft. - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

Observations (8)

DistanceCodeObservation
4.6SAV
98.3AMHJ 0305
4.6MGOMAG COAT
0MWL
98.3SAV
0MWM
0MGOCONNECTION AT MH 9 O'CLOCK
0AMHJ 0305A

Properties (6)

additional_info
SC398870
custom_field_two
3
customer
LACSD
datetime
2020-02-25T00:13:02-08:00
documentation
PROPIPE
is_lateral_inspection
false