Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Mar 20, 2020, 12:28 PM
  • 17 0007_17 0006_3202020_053117.mp4

Date
03/20/2020
W/O
0824033
Weather
Dry
Operator/Surveyor
REVELES
Sewer ID
Z00668
PipeID
P13732
Time
5:28 AM
Certificate
U-115-06022630
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
H1381
Sewer Name
17 DISTRICT #17 MAIN TRUNK
City
Altadena
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 17
Page No.
03
Purpose
Maintenance Related
Project
20200319VMR_DISTRICT_17_MAIN_TRUNK
Material
Vitrified Clay Pipe
Shape
Circular
Height
15 in.
Upstream MH
17 0007
Downstream MH
17 0006
Dir. of Survey
Downstream
Length Surveyed
287.8 ft.
Total Length
287.8 ft.
Structural Index
0
Structural Quick
0000
Structural Rating
0
O&M Index
1
O&M Quick
2113
O&M Rating
5
Overall Index
1
Overall Quick
Overall Rating
5
Pipe schematic from manhole 17 0007 to 17 0006
MH: 17 0007MH: 17 0006downstream0 ft. MWM - Water Mark, 20 %of cross sectional area0 ft. MWL - Water Level, 10 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 05:30 AM6.9 ft. RFC - Roots Fine Connection, from 02 to 03 o'clock, within 8 inches of joint: YES57.2 ft. RTJ - Roots Tap Joint, at 12 o'clock, 5 %, within 8 inches of joint: YESR75.5 ft. RFC - Roots Fine Connection, from 09 to 10 o'clock, within 8 inches of joint: YES79.7 ft. RFC - Roots Fine Connection, from 02 to 03 o'clock, within 8 inches of joint: YES287.8 ft. AMH - Downstream Manhole, Survey Ends - 05:45 AM

Observations (8)

DistanceCodeObservation
287.8AMH05:45 AM
79.7RFC
6.9RFC
75.5RFC
0MWM
0MWL
0AMH05:30 AM
57.2RTJ

Properties (4)

customer
LACSD
datetime
2020-03-20T05:28:26-07:00
documentation
REVELES, CASTILLO
is_lateral_inspection
false