Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Mar 3, 2020, 07:38 AM
  • 15 0764_15 0763 _03032020_005913.mp4

Date
03/02/2020
W/O
813447
Weather
Dry
Operator/Surveyor
M.MARTINEZ
Sewer ID
Z00593
PipeID
P12965
Time
11:38 PM
Certificate
U-115-06022794
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
K7363
Sewer Name
15 ARCADIA-SIERRA MADRE TRUNK, SECTS 2&5
City
ARCADIA
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 15
Page No.
08
Purpose
Routine Assessment
Project
RFIR_WO_813447_TV15146_FEB2020
Sewer Type
Gravity
Material
NRCP
Shape
Circular
Height
15 in.
Width
15 in.
Upstream MH
15 0764
Downstream MH
15 0763
Dir. of Survey
Downstream
Length Surveyed
353.1 ft.
Total Length
353.2 ft.
Structural Index
3
Structural Quick
3M2M
Structural Rating
346
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
3
Overall Quick
Overall Rating
346
Pipe schematic from manhole 15 0764 to 15 0763
MH: 15 0764MH: 15 0763downstream0 ft. MWL - Water Level, 20 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 15 07640 ft. MWM - Water Mark, 40 %of cross sectional area0 ft. MGO - General Observation - CONNECTION AT MH 9 O'CLOCK2 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start2 ft. MGO - General Observation - MAG COATING ATTATCHED9.5 ft. SSS - Surface Spalling, from 09 to 03 o'clock, within 8 inches of joint: YES, Start80.7 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: YES, 8"83.6 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: YES, 8"123.8 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: YES, 8"127.6 ft. TF - Tap Factory Made, at 01 o'clock, -, within 8 inches of joint: YES, 8"166.2 ft. TFC - Tap Factory Made Capped, at 01 o'clock, -, within 8 inches of joint: YES, 8"169 ft. TB - Tap Break-In, at 02 o'clock, -, within 8 inches of joint: YES, 8"169 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: YES, 8"199.8 ft. TF - Tap Factory Made, at 01 o'clock, -, within 8 inches of joint: YES, 8"266.4 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: YES, 8"269.7 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: YES, 8"350.1 ft. SSS - Surface Spalling, from 09 to 03 o'clock, within 8 inches of joint: YES, Finish350.1 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish353.2 ft. MGO - General Observation - CONNECTIONS AT BOTH 3 AND 9 O'CLOCK AT MH353.2 ft. AMH - Downstream Manhole, Survey Ends - 15 0763

Observation photos (3)

  • Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    2 ft. - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • General Observation - MAG COATING ATTATCHED

    2 ft. - General Observation - MAG COATING ATTATCHED

  • Surface Spalling, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

    9.5 ft. - Surface Spalling, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

Observations (21)

DistanceCodeObservation
123.8TF
169TB
266.4TF
353.2MGOCONNECTIONS AT BOTH 3 AND 9 O'CLOCK AT MH
269.7TFC
2SAV
199.8TF
127.6TF
166.2TFC
169TF
83.6TF
2MGOMAG COATING ATTATCHED
0MWL
350.1SSS
80.7TF
350.1SAV
0AMH15 0764
353.2AMH15 0763
0MWM
0MGOCONNECTION AT MH 9 O'CLOCK
9.5SSS

Properties (5)

custom_field_two
3
customer
LACSD
datetime
2020-03-02T23:38:08-08:00
documentation
PRO PIPE
is_lateral_inspection
false