Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Mar 3, 2020, 09:14 AM
  • 15 0759A_15 0759 _03032020_022644.mp4

Date
03/03/2020
W/O
813447
Weather
Dry
Operator/Surveyor
M.MARTINEZ
Sewer ID
Z00593
PipeID
P12961
Time
1:14 AM
Certificate
U-115-06022794
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
K7363
Sewer Name
15 ARCADIA-SIERRA MADRE TRUNK, SECTS 2&5
City
ARCADIA
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 15
Page No.
08
Purpose
Routine Assessment
Project
RFIR_WO_813447_TV15146_FEB2020
Sewer Type
Gravity
Material
NRCP
Shape
Circular
Height
15 in.
Width
15 in.
Upstream MH
15 0759A
Downstream MH
15 0759
Dir. of Survey
Downstream
Length Surveyed
157 ft.
Total Length
157 ft.
Structural Index
3
Structural Quick
3E2E
Structural Rating
155
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
3
Overall Quick
Overall Rating
155
Pipe schematic from manhole 15 0759A to 15 0759
MH: 15 0759AMH: 15 0759downstream0 ft. MWL - Water Level, 15 %of cross sectional area0 ft. MWM - Water Mark, 40 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 15 0759A0 ft. MGO - General Observation - CONNECTION AT MH 9 O'CLOCK2 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start2 ft. SSS - Surface Spalling, from 10 to 02 o'clock, within 8 inches of joint: YES, Start10 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: YES, 8"74.7 ft. TB - Tap Break-In, at 09 o'clock, -, within 8 inches of joint: YES, 8"80.4 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: YES, 8"83.6 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: YES, 8"110.9 ft. TB - Tap Break-In, at 02 o'clock, -, within 8 inches of joint: YES, 8"155.1 ft. SSS - Surface Spalling, from 10 to 02 o'clock, within 8 inches of joint: YES, Finish155.1 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish157 ft. AMH - Downstream Manhole, Survey Ends - 15 0759

Observation photos (2)

  • Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    2 ft. - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Surface Spalling, from 10 to 02 o'clock, within 8 inches of joint: YES, Start

    2 ft. - Surface Spalling, from 10 to 02 o'clock, within 8 inches of joint: YES, Start

Observations (14)

DistanceCodeObservation
10TFC
0MWL
0MWM
155.1SSS
74.7TB
0AMH15 0759A
110.9TB
2SAV
157AMH15 0759
83.6TFC
0MGOCONNECTION AT MH 9 O'CLOCK
155.1SAV
80.4TF
2SSS

Properties (5)

custom_field_two
3
customer
LACSD
datetime
2020-03-03T01:14:45-08:00
documentation
PRO PIPE
is_lateral_inspection
false