Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Mar 3, 2020, 09:27 AM
  • 15 0759_15 0758 _03032020_025339.mp4

Date
03/03/2020
W/O
813447
Weather
Dry
Operator/Surveyor
M.MARTINEZ
Sewer ID
Z00593
PipeID
P12960
Time
1:27 AM
Certificate
U-115-06022794
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
K7363
Sewer Name
15 ARCADIA-SIERRA MADRE TRUNK, SECTS 2&5
City
ARCADIA
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 15
Page No.
08
Purpose
Routine Assessment
Project
RFIR_WO_813447_TV15146_FEB2020
Sewer Type
Gravity
Material
NRCP
Shape
Circular
Height
15 in.
Width
15 in.
Upstream MH
15 0759
Downstream MH
15 0758
Dir. of Survey
Downstream
Length Surveyed
330.1 ft.
Total Length
330.1 ft.
Structural Index
3
Structural Quick
3L2L
Structural Rating
323
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
3
Overall Quick
Overall Rating
323
Pipe schematic from manhole 15 0759 to 15 0758
MH: 15 0759MH: 15 0758downstream0 ft. MWL - Water Level, 15 %of cross sectional area0 ft. MWM - Water Mark, 40 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 15 07592 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start5.1 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start19.1 ft. TB - Tap Break-In, at 10 o'clock, -, within 8 inches of joint: YES, 8"39.2 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: YES, 8"70.7 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: YES, 8"98.7 ft. TB - Tap Break-In, at 10 o'clock, -, within 8 inches of joint: YES, 8"119.4 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: YES, 8"121.7 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: YES, 8"183.8 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: YES, 8"186 ft. TB - Tap Break-In, at 10 o'clock, -, within 8 inches of joint: YES, 8"220.4 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: YES, 8"244.6 ft. TF - Tap Factory Made, at 11 o'clock, -, within 8 inches of joint: YES, 8"253.3 ft. TB - Tap Break-In, at 10 o'clock, -, within 8 inches of joint: YES, 8"308.1 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: YES, 8"327.2 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish327.2 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish330.1 ft. AMH - Downstream Manhole, Survey Ends - 15 0758

Observation photos (2)

  • Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    2 ft. - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    5.1 ft. - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

Observations (20)

DistanceCodeObservation
0MWL
0MWM
183.8TFC
70.7TFC
327.2SSS
5.1SSS
330.1AMH15 0758
98.7TB
2SAV
19.1TB
220.4TF
253.3TB
244.6TF
39.2TF
119.4TF
308.1TFC
186TB
327.2SAV
0AMH15 0759
121.7TFC

Properties (5)

custom_field_two
3
customer
LACSD
datetime
2020-03-03T01:27:59-08:00
documentation
PRO PIPE
is_lateral_inspection
false