Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Mar 6, 2020, 06:18 AM
  • 15 0789_15 0788 _03052020_232757.mp4

Date
03/05/2020
W/O
813447
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00593
PipeID
P12990
Time
10:18 PM
Certificate
U-508-7069
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K7480
Sewer Name
15 ARCADIA-SIERRA MADRE TRUNK, SECTS 2&5
City
ARCADIA
Loc. details
Main Highway - Urban
Location Code
A
Use of Sewer
Sanitary Sewer
District
District 15
Page No.
04
Purpose
Routine Assessment
Project
RFIR_WO_813447_TV15146_FEB2020
Sewer Type
Gravity
Material
NRCP
Shape
Circular
Height
15 in.
Width
15 in.
Upstream MH
15 0789
Downstream MH
15 0788
Dir. of Survey
Downstream
Length Surveyed
328.9 ft.
Total Length
328.9 ft.
Structural Index
3
Structural Quick
3100
Structural Rating
3
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
3
Overall Quick
Overall Rating
3
Pipe schematic from manhole 15 0789 to 15 0788
MH: 15 0789MH: 15 0788downstream0 ft. MWM - Water Mark, 20 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 15 07890 ft. MWL - Water Level, 10 %of cross sectional area2.3 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start5.1 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"5.6 ft. MGO - General Observation - MAG COAT90 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"319 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"328.9 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish328.9 ft. AMH - Downstream Manhole, Survey Ends - 15 0788

Observation photos (1)

  • Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    2.3 ft. - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

Observations (10)

DistanceCodeObservation
0MWM
0AMH15 0789
5.6MGOMAG COAT
5.1TFC
0MWL
90TF
319TF
328.9SAV
2.3SAV
328.9AMH15 0788

Properties (6)

additional_info
SC398887
custom_field_two
3
customer
LACSD
datetime
2020-03-05T22:18:43-08:00
documentation
PRO PIPE
is_lateral_inspection
false