Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Mar 6, 2020, 06:59 AM
  • 15 0785_15 0784_03062020_001248.mp4

Date
03/05/2020
W/O
813447
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00593
PipeID
P12985
Time
10:59 PM
Certificate
U-508-7069
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K7480
Sewer Name
15 ARCADIA-SIERRA MADRE TRUNK, SECTS 2&5
City
ARCADIA
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 15
Page No.
04
Purpose
Routine Assessment
Project
RFIR_WO_813447_TV15146_FEB2020
Sewer Type
Gravity
Material
NRCP
Shape
Circular
Height
15 in.
Width
15 in.
Upstream MH
15 0785
Downstream MH
15 0784
Dir. of Survey
Downstream
Length Surveyed
299.2 ft.
Total Length
299.2 ft.
Structural Index
3
Structural Quick
3100
Structural Rating
3
O&M Index
2
O&M Quick
3111
O&M Rating
4
Overall Index
2
Overall Quick
Overall Rating
7
Pipe schematic from manhole 15 0785 to 15 0784
MH: 15 0785MH: 15 0784downstream0 ft. MWM - Water Mark, 15 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 15 07850 ft. MWL - Water Level, 10 %of cross sectional area2.2 ft. MGO - General Observation - MAG COAT2.2 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start20.7 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"35.6 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"36.6 ft. TB - Tap Break-In, at 10 o'clock, -, within 8 inches of joint: NO, 6"72.2 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"72.2 ft. RML - Roots Medium Lateral, at 02 o'clock, 20 %, within 8 inches of joint: NO74.8 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"93.9 ft. RFL - Roots Fine Lateral, at 10 o'clock93.9 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"117.4 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"120.1 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"171.7 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"175.7 ft. TB - Tap Break-In, at 02 o'clock, -, within 8 inches of joint: NO, 6"180.5 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"217.4 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"219.7 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"223.2 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"268.5 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"271.6 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"299.1 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish299.2 ft. AMH - Downstream Manhole, Survey Ends - 15 0784

Observation photos (3)

  • Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    2.2 ft. - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Tap Break-In, at 10 o'clock, -, within 8 inches of joint: NO, 6"

    36.6 ft. - Tap Break-In, at 10 o'clock, -, within 8 inches of joint: NO, 6"

  • Tap Break-In, at 02 o'clock, -, within 8 inches of joint: NO, 6"

    175.7 ft. - Tap Break-In, at 02 o'clock, -, within 8 inches of joint: NO, 6"

Observations (25)

DistanceCodeObservation
219.7TF
117.4TF
72.2TF
93.9RFL
72.2RML
93.9TF
171.7TFC
268.5TF
0MWM
299.1SAV
74.8TFC
271.6TF
223.2TF
175.7TB
217.4TF
120.1TF
299.2AMH15 0784
2.2MGOMAG COAT
35.6TF
36.6TB
20.7TFC
180.5TFC
0AMH15 0785
0MWL
2.2SAV

Properties (6)

additional_info
SC398887
custom_field_two
3
customer
LACSD
datetime
2020-03-05T22:59:06-08:00
documentation
PRO PIPE
is_lateral_inspection
false