Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Feb 21, 2020, 09:05 AM
  • 01 1126_01 1125_02212020_021835.mp4

Date
02/21/2020
W/O
813509
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00210
PipeID
P01978
Time
1:05 AM
Certificate
U-508-7069
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K7462
Sewer Name
01 HUNTINGTON PARK TRUNK
City
CUDAHY
Loc. details
Main Highway - Urban
Location Code
A
Use of Sewer
Sanitary Sewer
District
District 01
Page No.
04
Purpose
Routine Assessment
Project
RFIR_WO_813509_TV01246_FEB2020
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
15 in.
Width
15 in.
Upstream MH
01 1126
Downstream MH
01 1125
Dir. of Survey
Downstream
Length Surveyed
281.5 ft.
Total Length
281.5 ft.
Structural Index
3
Structural Quick
3J21
Structural Rating
167
O&M Index
2
O&M Quick
2111
O&M Rating
3
Overall Index
3
Overall Quick
Overall Rating
170
Pipe schematic from manhole 01 1126 to 01 1125
MH: 01 1126MH: 01 1125downstream0 ft. MWL - Water Level, 5 %of cross sectional area0 ft. MWM - Water Mark, 10 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 01 11255 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start21.6 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"63.6 ft. RFL - Roots Fine Lateral, at 02 o'clock63.6 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"68.5 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"107 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: YES, 6", 6"114.2 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"145.2 ft. TB - Tap Break-In, at 02 o'clock, -, within 8 inches of joint: NO, 6"150.9 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"176.4 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"197 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"220 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"243 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"248.4 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"281 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES - Throughout the reach281 ft. SSS - Surface Spalling, from 09 to 03 o'clock, within 8 inches of joint: YES - Throughout the reach281.5 ft. AMH - Downstream Manhole, Survey Ends - 01 1125281.5 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish

Observation photos (1)

  • Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    5 ft. - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

Observations (21)

DistanceCodeObservation
145.2TB
63.6RFL
0MWL
21.6TF
63.6TF
248.4TF
197TF
114.2TF
281.5AMH01 1125
68.5TF
0MWM
281DAGSThroughout the reach
150.9TF
220TF
281.5CM
281SSSThroughout the reach
107TF
176.4TF
0AMH01 1125
5CM
243TF

Properties (6)

additional_info
SC398867
custom_field_two
3
customer
LACSD
datetime
2020-02-21T01:05:35-08:00
documentation
PROPIPE
is_lateral_inspection
false