Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Feb 21, 2020, 06:38 AM
  • 01 1081_01 0943_02202020_234814.mp4

Date
02/20/2020
W/O
813509
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00210
PipeID
P01930
Time
10:38 PM
Certificate
U-508-7069
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K7462
Sewer Name
01 HUNTINGTON PARK TRUNK
City
CUDAHY
Loc. details
Main Highway - Urban
Location Code
A
Use of Sewer
Sanitary Sewer
District
District 01
Page No.
08
Purpose
Routine Assessment
Project
RFIR_WO_813509_TV01246_FEB2020
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
24 in.
Width
24 in.
Upstream MH
01 1081
Downstream MH
01 0943
Dir. of Survey
Downstream
Length Surveyed
376.9 ft.
Total Length
376.9 ft.
Structural Index
3
Structural Quick
3X21
Structural Rating
383
O&M Index
2
O&M Quick
2100
O&M Rating
2
Overall Index
3
Overall Quick
Overall Rating
385
Pipe schematic from manhole 01 1081 to 01 0943
MH: 01 1081MH: 01 0943downstream0 ft. MWL - Water Level, 20 %of cross sectional area0 ft. MWM - Water Mark, 20 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 01 10814.4 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start109.2 ft. FL - Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Start367.4 ft. FL - Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Finish376 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES - Throughout the reach376 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES - Throughout the reach376.9 ft. AMH - Downstream Manhole, Survey Ends - 01 0943376.9 ft. MGO - General Observation - CONNECTION AT MH 9 O'CLOCK376.9 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish

Observation photos (2)

  • Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    4.4 ft. - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Start

    109.2 ft. - Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Start

Observations (11)

DistanceCodeObservation
0MWL
0MWM
376DAGSThroughout the reach
376.9AMH01 0943
0AMH01 1081
376.9MGOCONNECTION AT MH 9 O'CLOCK
367.4FL
4.4CM
376SSSThroughout the reach
376.9CM
109.2FL

Properties (6)

additional_info
SC398867
custom_field_two
3
customer
LACSD
datetime
2020-02-20T22:38:32-08:00
documentation
PROPIPE
is_lateral_inspection
false